Plan Review Notes For Permit 06040370 |
Permit Number |
06040370 |
|
Review Stop |
E |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2006-08-31 00:00:00 | ** UNSAT *** | | | | 1) NOTE: PLEASE SEE OCP ON TH GENERATOR | | SIZE IS AT 200A'S WHICH IS FEEDING #3'S. | | PLEASE SEE 240.21, AS TAPPED CONDUCTORS | | MUST TERMINATE IN OCP WHICH PROTECTS THE | | CONDUCTORS. | | PLEASE ALSO SEE AS THE EXISTING SUB | | PANELS DOES NOT INDICATE ANY SIZES , NOR | | DO THEY INDICATE A MCB WHICH WOULD ALSO | | LIMIT THE LOAD. | | PLEASE REVISE RISER. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE QUESTIONS, PLEASE | | CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|