Plan Review Notes
Plan Review Notes For Permit 06040370
Permit Number 06040370
Review Stop E
Sequence Number 5
Notes
Date Text
2006-08-31 00:00:00** UNSAT ***
  
 1) NOTE: PLEASE SEE OCP ON TH GENERATOR
 SIZE IS AT 200A'S WHICH IS FEEDING #3'S.
 PLEASE SEE 240.21, AS TAPPED CONDUCTORS
 MUST TERMINATE IN OCP WHICH PROTECTS THE
 CONDUCTORS.
 PLEASE ALSO SEE AS THE EXISTING SUB
 PANELS DOES NOT INDICATE ANY SIZES , NOR
 DO THEY INDICATE A MCB WHICH WOULD ALSO
 LIMIT THE LOAD.
 PLEASE REVISE RISER.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE QUESTIONS, PLEASE
 CALL.
  