Plan Review Notes
Plan Review Notes For Permit 06040370
Permit Number 06040370
Review Stop E
Sequence Number 4
Notes
Date Text
2006-08-09 00:00:00APPLS ROUTED TO ADRIANNA M.
 ** UNSAT **
  
 1) NOTE: PLEASE SEE ELECTRICAL RISER NOW
 INDICATES TWO NEW ATS'S WHICH WERE NEVER
 SUBMITTED FOR REVIEW.
 PLEASE SUBMIT SPECS/MANUFACTURES CUT
 SHEETS.
 110.3,90.8
 PLEASE ALSO CALRIFY RISER. PLEASE SEE
 RISER DOES NOT INDICATE WHERE FEEDERS GO
 TO LOADS. IT APPEARS THEY RUN BACK
 THROUGH THE MLO PANEL AND USING PANEL AS
 A RACEWAY.
 408.16.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  