Plan Review Notes For Permit 06040366 |
Permit Number |
06040366 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-05-15 00:00:00 | ** UNSAT ** | | | | 1) NOTE: PLEASE SEE NOTE #2 FROM | | PREVIOUS REVIEW. PLEASE SEE MISSING | | DISCONNECT FOR FEEDERS FROM GEN. | | PLEASE SEE THIS DISCONNECT SHALL BE | | GROUPED WITH EXISTING MAIN. | | PLEASE SEE 225.31-225.39 | | | | 2) NOTE: PLEASE SEE EXISTING GE SYSTEM | | IS NOW ONLY SHOWING A SINGLE GROUND ROD, | | HOWEVER IT IS KNOW TO THIS OFFICE THAT | | THE CWP SYSTEM IN THIS BUILDING IS | | METAL. PLEASE SEE 250.50, 250.52 ETC. | | PLEASE ALSO SEE A 2-GRND ROD WILL BE | | REQ'D. 250.56 | | | | 3) NOTE: PLEASE HIGH LIGHT ATS BEING | | INSTALLED, AS THE SPECS SUBMITTED | | INDICATE MORE THAN ONE UNIT. | | | | | | ** PLEASE SUBMIT TWO COMPLETE SETS WITH | | ALL NEW SHEETS INSERTED INTO THE | | COMPLETED SETS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | |
|