Plan Review Notes
Plan Review Notes For Permit 06040366
Permit Number 06040366
Review Stop E
Sequence Number 2
Notes
Date Text
2006-05-15 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE NOTE #2 FROM
 PREVIOUS REVIEW. PLEASE SEE MISSING
 DISCONNECT FOR FEEDERS FROM GEN.
 PLEASE SEE THIS DISCONNECT SHALL BE
 GROUPED WITH EXISTING MAIN.
 PLEASE SEE 225.31-225.39
  
 2) NOTE: PLEASE SEE EXISTING GE SYSTEM
 IS NOW ONLY SHOWING A SINGLE GROUND ROD,
 HOWEVER IT IS KNOW TO THIS OFFICE THAT
 THE CWP SYSTEM IN THIS BUILDING IS
 METAL. PLEASE SEE 250.50, 250.52 ETC.
 PLEASE ALSO SEE A 2-GRND ROD WILL BE
 REQ'D. 250.56
  
 3) NOTE: PLEASE HIGH LIGHT ATS BEING
 INSTALLED, AS THE SPECS SUBMITTED
 INDICATE MORE THAN ONE UNIT.
  
  
 ** PLEASE SUBMIT TWO COMPLETE SETS WITH
 ALL NEW SHEETS INSERTED INTO THE
 COMPLETED SETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  