Plan Review Notes
Plan Review Notes For Permit 06040366
Permit Number 06040366
Review Stop G
Sequence Number 1
Notes
Date Text
2006-04-29 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 ENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
  
 1)IF THIS IS AN EXISTING GAS METER
 ,PROVIDE THE TOTAL BTU LOAD, AND TOT.
 DEVELOPED LENGTH TO THE FURTHEST
 APPLIANCE.
 2) SHOW LOCATION OF GAS REGULATOR AND
 PROVIDE A MANFACTURE CUT SHEET, ALSO
 PURPOSE OF REGULATOR.
 3) 720 ISBTU'S / CU FT.TOTAL BTU'S IN
 ONE CU.FT. 1050 X 720 = 756 BTU'S /HR IS
 THE TOTAL BTU'S.
 4)FBC FUEL GAS 2004 TAB. 402.4 (20) FOR
 POLYETHYLENE PLASTIC PIPE, FOR 756- K
 BTU'S SHOULD BE 1-1/2" PE PIPE.
 5) SHOW THE LOCATION OF THE GAS METER ON
 SITE PLAN.
 END OF COMMENTS QUESTIONS 561-805-6692