Date |
Text |
2006-04-19 00:00:00 | ********** UNSAT *********** |
| |
| 1)NOTE: PLEASE PROVIDE LOAD CALCULATIONS |
| FOR EXISTING LOADS INTENDED FOR USE. |
| SINCE THE GEN WILL BE FEEDING THE ENTIRE |
| SERVICE, PLEASE SUBMIT LOAD CALCS |
| ACCORDINGLY. |
| PLEASE KNOW, AUTOMATIC LOAD SHEDDING IS |
| PERMITTED. |
| 702,220,215.5 |
| |
| 2) NOTE: PLEASE SEE EXISTING SERVICE IS |
| BEING SHOWN FEEDING ATS AND THEN BACK TO |
| THE SAME SERVICE?? THISIS NOT CLEAR |
| WHERE THIS FEEDER IS GOING AND WHERE THE |
| DISCONNECTING MEANS IS? |
| SERVICE AS SHOWN IS NOT CLEAR. |
| MEANS OF DISCONNECT FROM GEN? |
| GROUPING? |
| 230.76,230.76,230.70,230.72, |
| 225.31-225.39 |
| PLEASE KNOW, ALL MAINS AND DISCONNECTING |
| MEANS SHALL BE GROUPED. |
| (BRKR ON GEN IS NOT INCLUDED WITH THE |
| MEANS OF DISC.) |
| PLEASE PROVIDE A LAY OUT FOR SERVICE AND |
| LOCATION ON SITE. |
| |
| 3)NOTE: PLEASE PROVIDE THE OCP ON RISER |
| FOR GEN. (IT IS NOTED IN SPECS AT |
| 200A'S). |
| |
| 4) NOTE: PLEASE VERIFY THE GROUNDING |
| ELECTRODE SYSTEM AT SERVICE. |
| PLEASE SEE NOGE SYSTEM EXISTING OR |
| OTHERWISE IS BEING SHOWN. |
| 250.50,250.56, CWP? 2 GRND ROD? |
| |
| 5) NOTR: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT/MAINS. PLEASE SEE THAT |
| NEW MAIN AND EXISTING SERVICE MUST BE |
| RATED FOR THE AVAILABLE FUALT CURRENT |
| FROM FPL AND FROM GENERATOR. |
| 110.9, 215.5, NFPA-110 CHAPTER 7 |
| |
| |
| PLEASE SEE ANY OTHER COMMENTS FROM OTHER |
| TRADES WHICH MAY AFFECT PLANS. |
| IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |