Plan Review Notes For Permit 06040366 |
Permit Number |
06040366 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-05-04 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | TO THE FBC2004 | | | | 1.)PROVIDE ANCHORING INFORMATION TO | | COMPLY WITH FBC1609.1.3; STRUCTURAL | | MEMBERS AND SYSTEMS, AND COMPONENTS AND | | CLADDING IN A BUILDING OR STRUCTURE | | SHALL BE ANCHORED TO RESIST WIND-INDUCED | | OVERTURNING, UPLIFT AND SLIDING AND TO | | PROVIDE CONTINUOUS LOAD PATHS FOR THESE | | FORCES TO THE FOUNDATION.WHERE A | | PORTION OF THE RESISTANCE TO THESE | | FORCES IS PROVIDED BY DEAD LOAD, THE | | MINIMUM DEAD LOAD LIKELY TO BE IN PLACE | | DURING A DESIGN WIND EVENT SHALL BE | | USED. | | | | YOU HAVE PROVIDED INFORMATION IN REGARDS | | TO THE SLAB, AND PRODUCT INFORMATION WAS | | PROVIDED FOR TAPCONS, BUT THERE ARE | | SEVERAL DIFFERENT PRODUCTS ON THE SHEETS | | SUBMITTED WITH DIFFERENT VALUES. | | SPECIFY WHICH ANCHOR YOU ARE USING | | (CIRCLE) AND THE NUMBER OF ANCHORS TO BE | | USED. | | | | 2.)PROVIDE WIND DESIGN CRITERIA | | FBC1603.1.4. | | | | |
|