2006-05-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 1.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1609.1.3; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND
 CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE
 FORCES TO THE FOUNDATION.WHERE A
 PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE
 MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE
 USED.
  
 YOU HAVE PROVIDED INFORMATION IN REGARDS
 TO THE SLAB, AND PRODUCT INFORMATION WAS
 PROVIDED FOR TAPCONS, BUT THERE ARE
 SEVERAL DIFFERENT PRODUCTS ON THE SHEETS
 SUBMITTED WITH DIFFERENT VALUES.
 SPECIFY WHICH ANCHOR YOU ARE USING
 (CIRCLE) AND THE NUMBER OF ANCHORS TO BE
 USED.
  
 2.)PROVIDE WIND DESIGN CRITERIA
 FBC1603.1.4.
  
  