Date |
Text |
2006-07-22 00:00:00 | ** UNSAT ** |
| |
| ** PLEASE SEE SOME INFORMATION FROM |
| PREVIOUS REVIEW STILL NEEDS TO BE |
| ADDRESSED ALONG WITH NEW COMMENT(S). |
| |
| 1) NOTE: PLEASE SEE COMPLIANCE WITH FBC |
| CHAPTER 13 AS PREVIOUSLY NOTED. PLEASE |
| SEECOMPLIANCE WITH FBC CHAPTER 13 THEN |
| PLEASE SEE THE FOLLOWING: |
| 13-415.1.ABC.1.1, .1.2, AND .1.3 |
| PLEASE PROVIDE OVER-RIDES LOCATED AT THE |
| ENTRANCE INTO SPACE WHERE OCCUPANT CAN |
| CLEARLY SEE LIGHTING IN WHICH IS BEING |
| CONTROLLED. |
| PLEASE SEE SOME SYMBOLS ARE BEING SHOWN |
| AT DOORS HOWEVER THESE ARE NOT CLEAR AS |
| THEY COULD NOT BE LOCATED ON SYMBOL |
| LIST? |
| PLEASE SEE THAT TIME OF DAY SCHEDULING |
| CAN BE CHOSEN BY OCCUPANT. ALL OVER |
| RIDES IF ONMANUAL TIMED DEVICES MAY |
| ONLY A MAX OF 4HRS AND OCCUPANT TYPE |
| SENSORS MAY ONLY BE 30MINS. |
| PLEASE INDICATE THE MAX 30MINS.' |
| PLEASE SEE .1.3, AS SEPARATE SPACES |
| CONTAINING FLOOR TO CEILING HEIGHT |
| PARTITIONS REQUIRES CONTROLS AS NOTED. |
| PLEASE SEE PREVIOUS NOTE WHICH THE |
| ALLOWANCE AND DESIGN WATTAGE WAS IN |
| QUESTION. PLEASE CLARIFY AS WATTAGE IS |
| SHOWN OVER ALLOWANCE. |
| 13-415.2.ABC.1, 415.2.C.1, 415.2.B.1 |
| |
| 2) NOTE: PLEASE SEE PREVIOUS PLANS |
| INDICATED THE PANEL "D" AS EXISTING |
| ALTHOUGH NOTE MENTIONED NEW FEED FROM |
| EXSTING PANEL "G". PLEASE SEE PANEL "D" |
| IS NOW BEING SHOWN AS NEW. PLEASE SEE NO |
| LOAD CALCUALTIONS WERE SUBMITTED FOR |
| EXISTING PANEL "G" INDICATING NEW AND |
| EXISTING LOADS BEING ADDED. |
| PLEASE SUBMIT LOADS FOR PANEL "G" AND |
| SIZE OF PANEL ETC TO VERIFY NEW ADDED |
| LOADS. |
| 220,215.5,215.3,230.42 ETC. |
| FBC 106.1.2,106.3.5.1.2 |
| |
| 3) NOTE: PLEASE SEE COLOR CODING FOR |
| 277/480V SHALL BE BROWN, PURPLE, YELLOW. |
| SHOWN WITH ORANGE FOR "B" PHASE, YET |
| THISIS 277V NOT A "HIGH-LEG. |
| PLEASE ADJUST. PLEASE SEE THAT THIS CAN |
| BE REDLINED ALSO, AS NO 277V LIGHTING |
| ETC IS BEING SHOWN. |
| |
| 4) NOTE: PLEASE VERIFY LOAD ON RECEPT |
| CIRCUITS. PLEASE SEE SOME SHOWN AS |
| 13.5VA, HOWEVER @180 VA PER KNOW RECEPT |
| AND 9 ON EACH CIRCUIT THIS COMES UP TO |
| 1620VA. |
| PLEASE SEE 1,3,5,9,11, |
| |
| |
| ** PLEASE SEE 605 FOR ALL MODULAR |
| FURNITURE INSTALLATIONS.. |
| |
| ** PLEASE CALL TO GO OVER NOTE #1. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |