2006-08-01 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC RFLORIDA BUILDING CODE 2004 |
| RESIDENTIAL |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| NOTE - NEW PLAN SUBMITTED |
| |
| 1.)ROOMS/AREAS ARE TO BE LABELED AS TO |
| USE. |
| |
| 2.)THE SCOPE OF WORK IS NOT CLEAR. |
| ARE ALL OF THE WALLS AND DOORS SHOWN |
| NEW?NO WALL LEGEND WAS PROVIDED.ARE |
| THE INDIVIDUAL SPACES WALLS OR CUBICLES? |
| |
| 3.)PROVIDE DOOR DIMENSIONS, |
| FBC1008.1.1. |
| |
| 4.)ARE THE BATHROOMS NEW?IF THEY ARE |
| NEW OR ARE BEING RENOVATED, PROVIDE ALL |
| DETAILS FOR ACCESSIBILITY.FBC11-4.1.6. |
| |
| 5.)NO NOTES WERE MADE ON THE FLOOR |
| PLAN AS TO NEW OR EXISTING.IF THIS IS |
| A NEW FLOOR PLAN, THIS IS NOT A LEVEL I |
| ALTERATION.SEE FBC EB 303 AND 304. |
| SCOPE OF WORK IS NOT CLEAR. |
| |
| 6.)DOORS ARE TO COMPLY WITH |
| FBC11-4.13.6.THERE ARE SEVERAL DOORS |
| SHOWN WHICH DO NOT MEET THE MANEUVERING |
| CLEARANCE REQUIREMENT, SEE ALSO FBC11 |
| FIGURE 19. |
| |
| 7.)TENANT SEPARATION IS NOT CLEAR. |
| SHOW ANY REQUIRED FIRE RESISTANCE ON THE |
| PLAN. |
| |
| 8.)PROVIDE EXITING INFORMATION.THERE |
| ARE TWO DOORS AND A HALLWAY LEADING INTO |
| THE AREA SHOWN AS OPEN SPACE, BUT WHICH |
| IS PROBABLY A SECTION OF THE FLOOR WHICH |
| IS NOT UNDER THIS PERMIT. |
| |
| 9.)NEW COMMENTS WERE TRIGGERED DUE TO |
| NEW PLANS SUBMITTED.THE ARCHITECTURAL |
| PLANS WHICH WERE PREVIOUSLY REVIEWED |
| WERE NOT SUBMITTED, ONLY AN OLD FLOOR |
| PLAN FROM 1997.THE PREVIOUS PLAN |
| INDICATED A SCOPE OF WORK.THIS PLAN |
| SHOWS ONLY WALLS AND DOORS, AND SOME |
| DIMENSIONS, BUT DOES NOT GIVE |
| INFORMATION AS TO THE WORK TO BE DONE. |
| |
| 10.)FROM PREVIOUS REVIEW #4, SIGN |
| OWNER/AGENT LINE OF THE ENERGY CALCS, |
| FBC13-103.1. |
| |
| 11.)FROM PREVIOUS REVIEW #5, ON PAGE 5 |
| OF THE ENERGY CALC, EITHER INDICATE THAT |
| THESE ITEMS HAVE BEEN CHECKED OR WRITE |
| NA. |
| |
| 12.)SEE THE NOTE ON THE BOTTOM OF THE |
| ENERGY CALC, INPUT REPORT PRINTOUT FROM |
| ENERGY GUAGE COM MUST BE SUBMITTED WITH |
| THE COMPLIANCE REPORT. |
| |
| |
| |