| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} INDICATE IF CIRCUITS SHOWN ARE NEW OR |
| EXISTING. THE PANEL DESIGNATION "A", |
| DOES NOT CORRESPOND TO ANY OF THE PANEL |
| DESIGNATIONS(D G H F) SHOWN ON THE PLAN. |
| LOCATE PANEL "A" ON THE PLAN. |
| |
| 2} THE ENGINEER OF RECORD SHALL INDICATE |
| THE CERTIFICATE OF AUTHORIZATIONNUMBER |
| ALONG WITH OTHER INFORMATION REQUIRED BY |
| 61G15-23.002, FLORIDA ADMINISTRATIVE |
| CODE, IN THE TITLE BLOCK. |
| |
| 3} SHOW DIAGRAMATICALLY COMPLIANCE WITH |
| THE ENERGY CODE AS INDICATED IN THE |
| "LIGHTING KEYNOTES". PLACE THE DEVICES |
| ON THE DRAWING WHERE THE DESIGNER |
| INTENDS FOR THEM TO BE INSTALLED. SEE |
| THE REFERENCE TO THE " TORK #???" IS |
| UNACCEPTABLE. |
| |
| 4} PLEASE SEE PAGE 3, LIGHTING POWER |
| COMPLIANCE, ON FORM 400B, ATTACHED. THE |
| OPEN OFFICE ENTRY WITH EFFECTIVE @ 1960 |
| DOES NOT APPEAR TO COMPLY WITH THE |
| ALLOWANCE , WHICH IS SHOWN @ 1903. |
| |
| 5} AN ELECTRICAL CONTRACTOR IS REQUIRED |
| FOR THIS WORK AND MUST APPLY FOR A |
| SEPERATE PERMIT SINCE NOT SIGNED ON WITH |
| THE GC. |
| |