Plan Review Notes
Plan Review Notes For Permit 06040355
Permit Number 06040355
Review Stop E
Sequence Number 2
Notes
Date Text
2006-06-20 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE IF CIRCUITS SHOWN ARE NEW OR
 EXISTING. THE PANEL DESIGNATION "A",
 DOES NOT CORRESPOND TO ANY OF THE PANEL
 DESIGNATIONS(D G H F) SHOWN ON THE PLAN.
 LOCATE PANEL "A" ON THE PLAN.
  
 2} THE ENGINEER OF RECORD SHALL INDICATE
 THE CERTIFICATE OF AUTHORIZATIONNUMBER
 ALONG WITH OTHER INFORMATION REQUIRED BY
 61G15-23.002, FLORIDA ADMINISTRATIVE
 CODE, IN THE TITLE BLOCK.
  
 3} SHOW DIAGRAMATICALLY COMPLIANCE WITH
 THE ENERGY CODE AS INDICATED IN THE
 "LIGHTING KEYNOTES". PLACE THE DEVICES
 ON THE DRAWING WHERE THE DESIGNER
 INTENDS FOR THEM TO BE INSTALLED. SEE
 THE REFERENCE TO THE " TORK #???" IS
 UNACCEPTABLE.
  
 4} PLEASE SEE PAGE 3, LIGHTING POWER
 COMPLIANCE, ON FORM 400B, ATTACHED. THE
 OPEN OFFICE ENTRY WITH EFFECTIVE @ 1960
 DOES NOT APPEAR TO COMPLY WITH THE
 ALLOWANCE , WHICH IS SHOWN @ 1903.
  
 5} AN ELECTRICAL CONTRACTOR IS REQUIRED
 FOR THIS WORK AND MUST APPLY FOR A
 SEPERATE PERMIT SINCE NOT SIGNED ON WITH
 THE GC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/805-6731.