2006-10-04 00:00:00BUILDING REVIEW 2ND CHECKLIST:
  
 1- CONTRACTOR WROTE DOWN ON TOP OF DADE
 COUNTY NOA #02-0212.07 THAT SYSTEM TO BE
 INSTALLED IS ON PAGE 19. SYSTEM ON PAGE
 19 IS FOR TILE UNDERLAYMENT APPLICATION
 ONLY. THEREFORE, THIS SYSTEM DOESN'T
 WORK. SPECIFY OTHER SYSTEM THAT WORKS
 FOR PROPOSED INSTALLATION. COORDINATE
 INFORMATION WITH ENGINEER. SEE COMMENT
 #2 BELOW.
  
 2- ENGINEER TO SPECIFY SPECIFIC SYSTEM
 THAT HE'S REFERING TO IN ORDER TO VERIFY
 COMPLIANCE WITH THE SPECIFIED DESIGN
 PRESSURES AND ENHANCED FASTENING. PLEASE
 SPECIFY PAGE OF APPROVED ASSEMBLY.
  
 3- NOTICE OF COMMENCEMENT IS EXPIRED
 AFTER 90 DAYS OF BEING RECORDED IF WORK
 IS NOT STARTED. SEE SEC. 713.13(2) OF
 FLORIDA STATUTES.NEED TO PROVIDE
 RE-RECORDED NOTICE OF COMMENCEMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712