Plan Review Notes For Permit 06040349 |
Permit Number |
06040349 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-04-11 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1- PRODUCT APPROVAL LISTS SEVERAL | | APPROVED ASSEMBLIES FROM PAGE 7 THRU | | PAGE 19 OF THE DADE COUNTY NOA REPORT. | | NEED TO INCLUDE ONLY THE SPECIFIC | | ASSEMBLY THAT IS GOING TO BE INSTALLED. | | SEE ATTACHED COPY OF CITY POLICY AND | | REQUIREMENTS FOR RE-ROOF PERMITS. | | | | 2- IF SELECTED APPROVED ASSEMBLY IS | | LIMITED BY GENERAL LIMITATION #7, THEN | | NEED TO PROVIDE CALCULATIONS FOR | | ENHANCED FASTENING AT CORNER AND | | PERIMETER AREAS. 2 COPIES OF | | CALCULATIONS NEED TO BE SIGNED AND | | SEALED BY ANY OF THE PROFESSIONALS | | LISTED IN LIMITATION #7. SEE GENERAL | | LIMITATION #7 ON PAGE 20 OF 20 OF DADE | | COUNTY NOA. | | | | 3- IF SELECTED APPROVED ASSEMBLY IS | | LIMITED BY GENERAL LIMITATION #9, THEN | | ASSEMBLY CAN'T BE INSTALLED BECAUSE | | ADDITIONAL NAIL ENHANCING IS NOT | | ALLOWED. SEE GENERAL LIMITATION #9. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|