Plan Review Notes For Permit 06040316 |
Permit Number |
06040316 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-04-27 00:00:00 | *** DENIED *** | | 1) PLANS MAY NOT BE DONE IN PENCIL. | | | | 2) PLEASE SUBMIT SITE PLAN SHOWING | | PROPOSED LOCATION OF GENERATOR, SEE NOTE | | #3. | | | | 3)GENERATOR EXHUST MUST BE TEN FEET AWAY | | FROM ANY BUILDING OPENINGS (WINDOWS, | | DOORS, ROOF & EAVE VENTS), AND TEN FEET | | AWAY FROM ADJECENT BUILDING OPENS. PER | | 2004 FBC/M 401.5.1 . | | | | 4) SEE ELECTRICAL NOTE #4. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|