 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT ALL EQUIPMENT
 SPECIFICATIONS, GENERATOR AND TRANSFER
 SWITCH. IF THESE SPECS ARE GENERIC BE
 SURE TO HIGHLIGHT OR OTHERWISE INDICATE
 THE MODELS INTENDED TO BE USD.
  
 2} THE PLANS ARE NOT CLEAR. ONE SHEET
 INDICATES 2-200 AMP DISCONNECTS, FROM
 THE GENERATOR, FEEDING ATS'S, ANOTHER
 SHOWS 2-200 AMP DISCONNECTS FROM A
 GUTTER FEEDING THEM, WITH THE GENERATOR
 SIDE FEED NOT SHOWN.AND ANOTHER SHEET
 SHOWING 3-100 AMP PANELS OR DISCONNECTS
 (PLAN DOESN'T SAY), NOT FEEDING
 ANYTHING, APPARANTLY FED FROM THE SAME
 GUTTER AS THE 2-200 AMP DISCONNECTS ON
 THE PREVIOUS PAGE.
  
 PLEASE SUBMIT A SITE PLAN SHOWING ALL
 THIS EQUIPMENT AND WHAT IT FEEDS.
  
 3} THE HEAT LOAD ISN'T IN THE LOAD CALC.
 PLEASE INCLUDE, IF SMALLER THAN THE
 CONDENERLOADS , PLEASE INDICATE SAME.
  
 4} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE VALUE, LABOR AND MATERIAL OF
 THE ENTIRE INSTALLATION, INCLUDING THE
 GENERATOR, PAD AND ATS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  