| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} PLEASE SUBMIT ALL EQUIPMENT |
| SPECIFICATIONS, GENERATOR AND TRANSFER |
| SWITCH. IF THESE SPECS ARE GENERIC BE |
| SURE TO HIGHLIGHT OR OTHERWISE INDICATE |
| THE MODELS INTENDED TO BE USD. |
| |
| 2} THE PLANS ARE NOT CLEAR. ONE SHEET |
| INDICATES 2-200 AMP DISCONNECTS, FROM |
| THE GENERATOR, FEEDING ATS'S, ANOTHER |
| SHOWS 2-200 AMP DISCONNECTS FROM A |
| GUTTER FEEDING THEM, WITH THE GENERATOR |
| SIDE FEED NOT SHOWN.AND ANOTHER SHEET |
| SHOWING 3-100 AMP PANELS OR DISCONNECTS |
| (PLAN DOESN'T SAY), NOT FEEDING |
| ANYTHING, APPARANTLY FED FROM THE SAME |
| GUTTER AS THE 2-200 AMP DISCONNECTS ON |
| THE PREVIOUS PAGE. |
| |
| PLEASE SUBMIT A SITE PLAN SHOWING ALL |
| THIS EQUIPMENT AND WHAT IT FEEDS. |
| |
| 3} THE HEAT LOAD ISN'T IN THE LOAD CALC. |
| PLEASE INCLUDE, IF SMALLER THAN THE |
| CONDENERLOADS , PLEASE INDICATE SAME. |
| |
| 4} THE VALUE ON THE APPLICATION MUST |
| INCLUDE THE VALUE, LABOR AND MATERIAL OF |
| THE ENTIRE INSTALLATION, INCLUDING THE |
| GENERATOR, PAD AND ATS. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |