2006-04-13 00:00:00 | *** DENIED *** |
| 1) FOR REVIEW PURPOSES ONLY NOT FOR |
| PERMIT. |
| |
| 2) SEE ELECTRICAL COMMENT #1. |
| |
| 3) NEED TO SHOW ON MECHANICAL PLANS DUCT |
| SIZES AND CFM'S TO EACH SUPPLY AIR |
| GRILL. |
| |
| 4) PLEASEE SHOW ANY EXISTING A/C DUCTS |
| AND GRILLS IN THE WORK AREA AND LIST IF |
| THEY WILL BE RELOCATED OR REMOVED. |
| |
| 5) PROVIED FOR RETURN AIR TO EACH |
| ENCLOSED AREA, SEE NOTE #6. |
| |
| 6)BALANCED RETURN AIR. |
| THIS MAY BE ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| INCREASING THE RETURN TRANSFER ONE AND |
| ONE HALF TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING |
| AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| PROPER RETURN AIR BALANCE. |
| (B)TRANSFER GRILLES SHALL USE 50 |
| SQUARE INCHES (OF GRILLE AREA) TO 100 |
| CFM (OF SUPPLY AIR) FOR SIZING |
| THROUGH-THE-WALL TRANSFER GRILLES AND |
| USING AN UNRESTRICTED 1-INCH |
| UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| RETURN AIR BALANCE |
| (C)HABITABLE ROOMS ONLY SHALL BE |
| REQUIRED TO MEET THESE REQUIREMENTS FOR |
| PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| AIR INTO THE MASTER SUITE SHALL BE |
| INCLUDED. PER 2004 FBC/R M1602.4 . |
| |
| MECHANICAL PLAN REVIEW BY; |