Plan Review Notes
Plan Review Notes For Permit 06040288
Permit Number 06040288
Review Stop B
Sequence Number 1
Notes
Date Text
2006-04-27 00:00:00BUILDING PROVISO:
 TO BE IN PLACE AT C.O.:
  
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE PROVIDED
 WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH 424.2.17.1.14.
  
 424.2.17.1.5 CHILD SAFETY BARRIER
 ASTM D5034 100 LB TENSILE STRNGTH
 ASTM D3787 150 LB BALL BURST
 STRENGTH
  
 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.
  
 3)424.1.3.1.2
 POOL WET DECKS SHALL BE UNIFORMLY SLOPED
 AT A MINIMUM OF 2 PERCENT TO A MAXIMUM
 OF 4 PERCENT AWAY FROM THE POOL OR TO
 DECK DRAINS TO PREVENT STANDING WATER.
 WHEN A CURB IS PROVIDED, THE DECK SHALL
 NOT BE MORE THAN 10 INCHES (254 MM)
 BELOW THE TOP OF THE CURB.