Plan Review Notes
Plan Review Notes For Permit 06040268
Permit Number 06040268
Review Stop P
Sequence Number 1
Notes
Date Text
2006-04-24 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING INFORMATION IS REQURED FOR
 PLAN REVIEW FOR A PLUMBING PERMIT:
  
 1. TWO (2) SETS OF PLANS ARE REQUIRED
 FOR PLAN REVIEW PER 106.1, FBC-2004.
 2. PLANS REQUIRE THE PRINTED NAME AND
 SIGNITURE OF THE PERSON TAKING
 RESPONSIBILITY OF DRAWINGS, PER FBC-2004
 AND FLORIDA STATUTES 471.
 3. NEED TO INDICATE PROPOSED PLUMBING
 LAYOUT OF BATHROOM AND LAUNDRY ROOM
 INDICATING DOORS ON FLOOR PLAN.
 4. THE SANITARY RISER DIAGRAM SUBMITTED
 INDICATES A 2" DRY VENT STACK THAT NEEDS
 TO BE ELIMINATED. THE NEW LAV. INDICATED
 ON DRAWING NEEDS TO VENT THROUGH THE
 ROOF PER 909.1
 5. THE NEW LAUNDRY NEEDS TO BE ADDED TO
 THE ISOMETRIC SANITARY RISER DIAGRAM.
 NOTE: PER 406.3 THE WASHING MACHINE
 WASTE CONNECTION SHALL BE 2", AND THE
 DRAINAGE STACK MINIMUM 3", AND SHALL
 DISCHARGE DOWNSTREAM OF THE BATHROOM
 GROUP WET VENT.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved