2006-05-19 00:00:00 | DENIED |
| |
| |
| 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 2.PERMIT VALUATION SHOULD INCLUDE ALL |
| MATERIALS AND LABOR FOR THE PROJECT. |
| REVISE PERMIT VALUE AND PAY ADDITIONAL |
| PERMIT FEES. |
| |
| 3.SUBMIT TWO COPIES OF ENERGY CALCS |
| PER 2004 FBC. |
| |
| 4.TWO COPIES OF PRODUCT APPROVALS |
| REQUIRED FOR SHUTTERS, ROOFING AND |
| STRAPS AND TIEDOWNS. |
| |
| 5.ALL PRODUCT APPROVALS SUBMITTED WITH |
| QUALITY ASSURANCE SHALL HAVE THE |
| FOLLOWING STATE APPROVAL ATTACHED. |
| |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A STATE PRODUCT APPROVAL |
| SHEETS THAT LISTS THE PRODUCT IDENTITY |
| NUMBER FROM THE STATE. IF THE PRODUCT |
| DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT |
| AN APPLICATION FOR LOCAL PRODUCT |
| APPROVAL OR SITE SPECIFIC FORM PER RULE |
| 9B-72. SEE ATTACHMENT. |
| WWW.FLORIDABUILDING.ORG |
| |
| 6.THOSE PRODUCT APPROVALS WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL.WPB |
| AMENDMENT TO FBC 106.3.3. |
| |
| 7.A DESIGN PROFESSIONAL OR AN OWNER |
| MUST ELECT ONE OR A COMBINATION OF |
| LEVELS OF ALTERATION PURSUANT TO |
| SECTIONS 303, 304 AND 305 OF THIS CODE. |
| SHOW HOW PLANS WILL COMPLY WITH THE |
| SECTION(S) SELECTED.2004 FBC EXISTING |
| BUILDING 301.5 |
| |
| 8.SUBMIT A WINDOW AND SHUTTER SCHEDULE |
| SHOWING SIZES AND TYPES OF WINDOWS AND |
| LOCATION OF BEDROOM WINDOWS. |
| |
| 9.SUBMIT TWO ORIGONAL SIGNED AND |
| SEALED SURVEYS FS. 472.025 |
| |
| 10.INSUFFIENT INFORMATION SUBMITTED |
| FOR A COMPLETE PLAN REVIEW. SEE THE |
| FOLLOWING SECTIONS FORM THE WPB |
| AMMENDMENTS TO THE 2004 FBC. |
| 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| BUILDINGS. THE EXAMINATION OF THE |
| DOCUMENTS BY THE BUILDING OFFICIAL SHALL |
| INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; |
| FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN |
| OR TRUSS LAYOUT; AND ALL EXTERIOR |
| ELEVATIONS: |
| ALL SHOW EXISTING AREAS, NEW AREAS. |
| SHOW COMPLIANCE WITH CHAPTER 16 FOR |
| WINDLOAD AND PRESSURES. |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. SUBMIT ONE COPY OF |
| OLD PAGES FOR REFERENCE. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET |
| OR SPECIFICATION PAGE WHERE THE CHANGES |
| CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |