Plan Review Notes
Plan Review Notes For Permit 06040232
Permit Number 06040232
Review Stop M
Sequence Number 1
Notes
Date Text
2006-04-19 00:00:00*** DENIED ***
 1) NEED TO PASS ZONING.
  
 2) GENERATOR EXHUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF & EAVE VENTS), AND
 TEN FEET AWAY FROM ADJECENT BUILDING
 OPENS. PER 2004 FBC/M 401.5.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved