Plan Review Notes For Permit 06040215 |
Permit Number |
06040215 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-04-24 00:00:00 | DENIED; | | 1.WOMANS BATHROOM FACILITIES DO NOT | | COMPLY WITH FBC-2004 PLUMBING TABLE | | 403.1 #1 A-3. (WOMANS ROOM NOT SHOWN) | | MUST COMPLY WITH SEC403.2. | | 2.DRINKING FOUNTAIN REQUIRED PER TABLE | | 403.1. BOTTLE WATER CANNOT REPLACE THE | | FIRST DRINKING FOUNTAIN PER SEC. 410.1 | | THE BOTTLE COOLER CAN BE USED ON THE 2ND | | FLOOR. | | 3.WATER RISER DIAGRAM IS REQUIRED PER | | FBC-2004 CHAPTER 1, ADMINISTRATION CODE, | | SEC.106.3.5.1.3. | | 4.SANITARY RISER DIAGRA, URINALS ARE NOT | | VENTED. THE 3" BUILDING DRAIN FROM THE | | URINAL TO THE W/C DRAIN IS REQUIRED TO | | BE 3" FOR VENTING SEE TABLE 909.3 WET | | VENT SIZING. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|