Plan Review Notes For Permit 06040215 |
Permit Number |
06040215 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-04-26 00:00:00 | ******DENIED****** | | | | 1) THE MAIN ENTRANCE DOORS SWING AGAINST | | THE DIRECTION OF TRAVEL. EXIT DOORS | | SERVING AN OCCUPANT LOAD OF 50 OR MORE | | SHALL SWING IN THE DIRECTION OF TRAVEL. | | NFPA 101, SECTION 7.2.1.4.2. | | | | 2) LIFE SAFETY SHALL COMPLY WITH NFPA | | 101, 2003 EDITION. | | | | 3) PLEASE ILLUSTRATE THE MAXIMUM TRAVEL | | DISTANCES ON LIFE SAFETY SHEETS. | | | | 4) PLEASE INDICATE THE MINIMUM INTERIOR | | FINISH CLASSIFICATION FOR WALLS AND | | CEILINGS. | | | | 5) SECOND FLOOR LIFE SAFETY PLAN | | ILLUSTRATES PERSONS BEING DIRECTED | | ACROSS THE FIRST FLOOR ROOF TO STAIRS | | THAT AREN'T MARKED AN EXIT. PLEASE | | EXPLAIN RATIONALE. | | | | 6) IS THIS BUILDING PROTECTED BY FIRE | | SPRINKLER AND FIRE ALARM SYSTEMS? | | | | 7) DOORS SERVING AREAS WITH OCCUPANT | | LOAD GREATER THAN 100 SHALL HAVE PANIC | | HARDWARE. IS THIS AN EXISTING CONDITION? | | NO DOOR SCHEDULE FOUND ON PLANS. | | | | 8) WILL THE NEW FRENCH DOORS CONFLICT | | WITH THE EXISTING STAIR DOOR? | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|