Plan Review Notes
Plan Review Notes For Permit 06040215
Permit Number 06040215
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-04-26 00:00:00******DENIED******
  
 1) THE MAIN ENTRANCE DOORS SWING AGAINST
 THE DIRECTION OF TRAVEL. EXIT DOORS
 SERVING AN OCCUPANT LOAD OF 50 OR MORE
 SHALL SWING IN THE DIRECTION OF TRAVEL.
 NFPA 101, SECTION 7.2.1.4.2.
  
 2) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 3) PLEASE ILLUSTRATE THE MAXIMUM TRAVEL
 DISTANCES ON LIFE SAFETY SHEETS.
  
 4) PLEASE INDICATE THE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 5) SECOND FLOOR LIFE SAFETY PLAN
 ILLUSTRATES PERSONS BEING DIRECTED
 ACROSS THE FIRST FLOOR ROOF TO STAIRS
 THAT AREN'T MARKED AN EXIT. PLEASE
 EXPLAIN RATIONALE.
  
 6) IS THIS BUILDING PROTECTED BY FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS?
  
 7) DOORS SERVING AREAS WITH OCCUPANT
 LOAD GREATER THAN 100 SHALL HAVE PANIC
 HARDWARE. IS THIS AN EXISTING CONDITION?
 NO DOOR SCHEDULE FOUND ON PLANS.
  
 8) WILL THE NEW FRENCH DOORS CONFLICT
 WITH THE EXISTING STAIR DOOR?
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722