2006-05-01 00:00:00 | 1)EXISTING BUILDING CODE 304.1 SCOPE. |
| LEVEL 2 ALTERATIONS INCLUDE THE |
| RECONFIGURATION OF SPACE, THE ADDITION |
| OR ELIMINATION OF ANY DOOR OR WINDOW, |
| THE RECONFIGURATION OR EXTENSION OF ANY |
| SYSTEM, OR THE INSTALLATION OF ANY |
| ADDITIONAL EQUIPMENT. LEVEL 2 |
| ALTERATIONS SHALL COMPLY WITH CH.5 AND |
| CH.6. |
| |
| 2) 605.4.2 DOOR SWING . |
| IN THE WORK AREA AND IN THE EGRESS PATH |
| FROM ANY WORK AREA TO THE EXIT |
| DISCHARGE, ALL EGRESS DOORS SERVING AN |
| OCCUPANT LOAD GREATER THAN 50 SHALL |
| SWING IN THE DIRECTION OF EXIT TRAVEL. |
| SEE EGRESS DOORS ON PAGES 2/6 AND 5/6. |
| THE NEW FRENCH DOORS CANNOT SWING INTO |
| THE DOOR LEADING FROM THE STAIR-WAY. |
| THIS DESIGN WILL NOT MEET EGRESS |
| REQUIREMENTS.FBC.1008.1.8.8/1008.1.9 |
| |
| 3) SHEET 2/6 SHOWS A NEW WALL AT THE END |
| OF THE HALL WAY, HOWEVER, ON SHEETS E-2 |
| AND E-4 THE WALL IS NOT SHOWN. THE FLOOR |
| LAY-OUT SHOULD SHOW THE SAME DESIGN ON |
| EACH PAGE. |
| |
| 4) WILL THE EXIT ACCESS ON THE SECOND |
| FLOOR LEAD TO THE ROOF? PLEASE SHOW IF |
| THERE IS A HALLWAY OR CORRIDOR LEADING |
| TO THE STAIRWAY IS THERE A PANIC LATCH |
| ON THE DOOR LEADING TO THE STAIRS? THAT |
| PATH OF TRAVEL WHICH LEADS TO THE ROOF |
| NEEDS MORE DETAILS. |
| FBC.1008.1.8 DOOR OPERATIONS. |
| EXCEPT AS SPECIFICALLY PERMITTED BY THIS |
| SECTION EGRESS DOORS SHALL BE READILY |
| OPENABLE FROM THE EGRESS SIDE WITHOUT |
| THE USE OF A KEY OR SPECIAL KNOWLEDGE OR |
| EFFORT. |
| |
| 5) IS THERE A WORKING AUTOMATIC |
| SPRINKLER SYSTEM INSTALLED IN THE |
| BULDING? |
| |