Plan Review Notes
Plan Review Notes For Permit 06040214
Permit Number 06040214
Review Stop B
Sequence Number 1
Notes
Date Text
2006-04-26 00:00:001) ALL CONSTRUCTION DOCUMENTS BEING
 FILED FOR PUBLIC RECORD SHALL BE OF
 SUFFICIENT CLARITY. SEE THE SHEETS
 D-1/A-1/A-2 AND A-3. THERE IS NO
 INFORMATION ON THE SEAL.
  
 (2) 481.221SEALS;DISPLAY OF
 CERTIFICATE NUMBER.--
 (2)EACH REGISTERED ARCHITECT SHALL
 OBTAIN ONE SEAL IN A FORM APPROVED BY
 RULE OF THE BOARD AND MAY, IN ADDITION,
 REGISTER HER OR HIS SEAL ELECTRONICALLY
 IN ACCORDANCE WITH SS. 668.001-668.006.
 ALL FINAL CONSTRUCTION DOCUMENTS AND
 INSTRUMENTS OF SERVICE WHICH INCLUDE
 DRAWINGS, PLANS, SPECIFICATIONS, OR
 REPORTS PREPARED OR ISSUED BY THE
 REGISTERED ARCHITECT AND BEING FILED FOR
 PUBLIC RECORD SHALL BEAR THE SIGNATURE
 AND SEAL OF THE REGISTERED ARCHITECT WHO
 PREPARED OR APPROVED THE DOCUMENT AND
 THE DATE ON WHICH THEY WERE SEALED. THE
 SIGNATURE, DATE, AND SEAL SHALL BE
 EVIDENCE OF THE AUTHENTICITY OF THAT TO
 WHICH THEY ARE AFFIXED.
 (8)FINAL CONSTRUCTION DOCUMENTS OR
 INSTRUMENTS OF SERVICE WHICH INCLUDE
 PLANS, DRAWINGS, SPECIFICATIONS, OR
 OTHER ARCHITECTURAL DOCUMENTS PREPARED
 BY A REGISTERED ARCHITECT AS PART OF HER
 OR HIS ARCHITECTURAL PRACTICE SHALL BE
 OF A SUFFICIENTLY HIGH STANDARD TO
 CLEARLY AND ACCURATELY INDICATE OR
 ILLUSTRATE ALL ESSENTIAL PARTS OF THE
 WORK TO WHICH THEY REFER.
  
 3) DOOR #116 ON SHEET A-1 SHOWS A LEFT
 SWING HOWEVER, ON SHEETS E2.1 AND E3.1
 THE SAME DOOR SHOWS A RIGHT SWING.
 PLEASE SHOW MATCHING FLOOR LAY-OUT ON
 ALL FLOOR PLANS. 11-4.13.6 MANEUVERING
 CLEARANCES AT DOORS. MINIMUM MANEUVERING
 CLEARANCES AT DOORS THAT ARE NOT
 AUTOMATIC OR POWER-ASSISTED SHALL BE AS
 SHOWN IN FIGURE 11-25 . THE FLOOR OR
 GROUND AREA WITHIN THE REQUIRED
 CLEARANCES SHALL BE LEVEL AND CLEAR.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  