Date |
Text |
2006-04-26 00:00:00 | 1) ALL CONSTRUCTION DOCUMENTS BEING |
| FILED FOR PUBLIC RECORD SHALL BE OF |
| SUFFICIENT CLARITY. SEE THE SHEETS |
| D-1/A-1/A-2 AND A-3. THERE IS NO |
| INFORMATION ON THE SEAL. |
| |
| (2) 481.221SEALS;DISPLAY OF |
| CERTIFICATE NUMBER.-- |
| (2)EACH REGISTERED ARCHITECT SHALL |
| OBTAIN ONE SEAL IN A FORM APPROVED BY |
| RULE OF THE BOARD AND MAY, IN ADDITION, |
| REGISTER HER OR HIS SEAL ELECTRONICALLY |
| IN ACCORDANCE WITH SS. 668.001-668.006. |
| ALL FINAL CONSTRUCTION DOCUMENTS AND |
| INSTRUMENTS OF SERVICE WHICH INCLUDE |
| DRAWINGS, PLANS, SPECIFICATIONS, OR |
| REPORTS PREPARED OR ISSUED BY THE |
| REGISTERED ARCHITECT AND BEING FILED FOR |
| PUBLIC RECORD SHALL BEAR THE SIGNATURE |
| AND SEAL OF THE REGISTERED ARCHITECT WHO |
| PREPARED OR APPROVED THE DOCUMENT AND |
| THE DATE ON WHICH THEY WERE SEALED. THE |
| SIGNATURE, DATE, AND SEAL SHALL BE |
| EVIDENCE OF THE AUTHENTICITY OF THAT TO |
| WHICH THEY ARE AFFIXED. |
| (8)FINAL CONSTRUCTION DOCUMENTS OR |
| INSTRUMENTS OF SERVICE WHICH INCLUDE |
| PLANS, DRAWINGS, SPECIFICATIONS, OR |
| OTHER ARCHITECTURAL DOCUMENTS PREPARED |
| BY A REGISTERED ARCHITECT AS PART OF HER |
| OR HIS ARCHITECTURAL PRACTICE SHALL BE |
| OF A SUFFICIENTLY HIGH STANDARD TO |
| CLEARLY AND ACCURATELY INDICATE OR |
| ILLUSTRATE ALL ESSENTIAL PARTS OF THE |
| WORK TO WHICH THEY REFER. |
| |
| 3) DOOR #116 ON SHEET A-1 SHOWS A LEFT |
| SWING HOWEVER, ON SHEETS E2.1 AND E3.1 |
| THE SAME DOOR SHOWS A RIGHT SWING. |
| PLEASE SHOW MATCHING FLOOR LAY-OUT ON |
| ALL FLOOR PLANS. 11-4.13.6 MANEUVERING |
| CLEARANCES AT DOORS. MINIMUM MANEUVERING |
| CLEARANCES AT DOORS THAT ARE NOT |
| AUTOMATIC OR POWER-ASSISTED SHALL BE AS |
| SHOWN IN FIGURE 11-25 . THE FLOOR OR |
| GROUND AREA WITHIN THE REQUIRED |
| CLEARANCES SHALL BE LEVEL AND CLEAR. |
| |