Plan Review Notes For Permit 06040152 |
Permit Number |
06040152 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-05-04 00:00:00 | **********DENIED********************* | | | | 1) NEW STAIRS MUST COMPLY WITH NFPA 101 | | TABLE 7.2.2.1 (A) MINIMUM WIDTH (44") OR | | (36") WHERE TOTAL OCCUPANT LOAD OF ALL | | STORIES SERVED BY STAIRWAYS IS FEWER | | THAN 50. | | | | 2) EGRESS DOORS SHALL COMPLY WITH NFPA | | 101 CHAPTER 7. | | | | | | NATE MCCRAY, ASSISTANT FIRE MARSHAL | | 561-804-4754 |
|