Plan Review Notes For Permit 06040152 |
Permit Number |
06040152 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-05-03 00:00:00 | ************** UNSAT ************* | | | | 1) NOTE: PLEASE SEE FS 481.221 WHICH | | REQUIRESTHE SIGNATURE , DATE AND SEAL | | OF SAID ARCHITECT ON TITLE BLOCKS . | | | | 2) NOTE: PLEASE PROVIDE MEANS OF EGRESS | | LIGHTING TO THE PUBLIC RIGHT OF WAY. | | PLEASE KNOW, A BATTERY BACK UP FIXTURE | | OF SOME SORT FOR STAIRS IS ALSO | | REQUIRED. | | PLEASE SEE THAT 10 FT CANDLES MININUM IS | | REQUIRED UNDER NORMAL POWER AND 1 FT | | CANDLE MINUNDER EM POWER CONDITIONS. | | PLEASE SEE 2003 NFPA-101 7.8.1.3,7.9.2.2 | | | | 3)NOTE: PLEASE SEE FIRE REVIEW COMMENTS | | ALSO WITH RESPECT TO ANY NEW OR EXISTING | | EXT LT FROM EXISTING EXT IN BUILDING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|