Plan Review Notes
Plan Review Notes For Permit 06040152
Permit Number 06040152
Review Stop B
Sequence Number 1
Notes
Date Text
2006-05-03 00:00:00 
  
 DENIED
  
 1) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 2) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 3) A DESIGN PROFESSIONAL THAT IS
 REGISTERED TO PRACTICE UNDER CHAPTER 481
 OR 471 OF THE FLORIDA STATUTES SHALL
 AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND
 DATE TO SAID DRAWINGS AND SPECIFICATIONS
 PER 106 FBC 2004
  
 4) PROVIDE LAYOUT OF BUILDING WITH
 CONSTRUCTION TYPE, OCCUPANCY
 CLASSIFICATION, OCCUPANT LOAD,ETC.
  
 5) PROVIDE SURVEY/SITE PLAN THAT SHOWS
 PROPERTY LINES
  
 6) STAIR WIDTH SHALL BE 44" PER 1009.1
 FBC UNLESS NOTE #4 REQUIREMENTALLOW
 FOREXCEPTIONS
  
 7) PROVIDE STAIR DETAILS SHOW COMPLIANCE
 WITH 1009.3 FOR TREAD WIDTH, (MIN 11")
 AND 1009.3.2, (SOLID RISERS) OF FBC
  
 8) PROVIDE DETAILS FOR HANDRAILS TO SHOW
 COMPLIANCE WITH 1009.11.1, (34"-38" HT.)
 1009.11.5, (CONTINUITY) AND 1012.3,
 (OPENING LIMITATIONS) OF FBC
  
 9) STAIRS SHALL HAVE HANDRAILS ON BOTH
 SIDES PER 1009.11 FBC
  
 10) EXIT DOORS SHALL BE MARKED WITH AN
 APPROVED SIGN THAT COMPLIES WITH 1006.3
 FBC
  
 BLDG PLAN REVIEW