Plan Review Notes For Permit 06040115 |
Permit Number |
06040115 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-04-12 00:00:00 | *******UNSAT ******* | | | | 1) NOTE: PLEASE INCLUDE LOCATIONS OF ALL | | SERVICE EQUIPMENT AS SHOWN ON RISER ON | | THE PROVIDED SITE LAYOUT. PLEASE SEE | | PLANS, AT CURRENT TIME ONLY INDICATE THE | | ATS ON THE OUTSIDE OF DWELLING. | | 215.5 | | | | 2) NOTE: PLEASE SEE RISER SUBMITTED DOES | | NOT SHOW HOW THE SYSTEM WILL TRANSFER. | | PLEASE SEE LINE AND LOAD FROM MAIN TO | | THE PANEL BEING FED FROM GEN DO NOT GO | | THROUGHT THE ATS. | | 215.5 PLEASE ADJUST RISER. | | | | 3) NOTE: PLEASE SEE CONDUCTORS SHOWN AS | | 3- #2/3'S?? PLEASE SEE 310.16 FOR MIN | | AGW SIZES AND ADJUST. | | 215.5 | | | | 4) NOTE: PLEASE INCLUDE DISCONNECTING | | MEANS FROM GEN TO SSERVICE/ATS LOCATED | | ON HOUSE GROUPED WITH EXISTING MAINS. | | THIS DISCONNECTING MEANS IS NOT REQUIED | | TO CONTAIN OCP , ONLY DISC. | | 225.31-225.39. | | | | 5) NOTE: PLEASE INDICATE THE ATS BEING | | USED FROM SPECS. | | PLEASE INDICATE THE AIC RAITNG FOR ATS. | | NFPA-110, 6.5.2, NEC 110.9 | | 215.5 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW., IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | | |
|