2006-05-16 00:00:00** UNSAT ON HOLD **
  
  
 1) NOTE: PLEASE SEE SPECS SUBMITTED DO
 NOT SHOW OR INDICATE THE NEX GEAR AS
 MENTIONED IN THE RESPONSE LTR. THE SPEC
 SUBMITTED SHOWS EQUIPMENT RATED FOR A
 NEMA 1 LOCATION AND NO BRKRS OR MANUAL
 MEANS OF DISCONNECT IS SHOWN.
 PLEASE SEE 230.76,230.79, 110.27 ETC.
  
 PLEASE KNOW, CALLED THE ENGINEER OF
 RECORD, AND HE IS TO SEND
 INFORMATION/SPECS VIA E-MAIL ASAP.
  
 PLANS ARE UNDER "P" IN THE LARGE BINS ON
 HOLD PENDING SPECS.
  