2006-05-03 00:00:00 | *** UNSAT *** |
| |
| |
| ** PLEASE SEE MOST COMMENTS FROM FIRST |
| REVIEW HAVE BEEN ADDRESSED, HOWEVER |
| PLEASE SEE NOTESBELOW. |
| |
| 1) NOTE: PLEASE SEE PREVIOUS COMMENT |
| WHICH REQUESTED CLARIFICATION OFTHE |
| APS CONTAINING A MANUAL MEANS OF |
| DISCONNECT LOCATED ON THE OUTSIDE OF |
| EQUIPMENT RATED FOR THE LOAD SERVED. |
| THE RESPONSE ONLY MENTIONED THE TRANSFER |
| SWITCH CONTAIN MOLDED CASE BRKRS FOR |
| MANUAL DISCONNECT, HOWEVER SPECS |
| SUBMITTED DO NOT CORRELATE WITH THIS. |
| PLEASE ALSO CLARIFYON THE OUTSIDE OF |
| EQUIPMENT WITHOUT EXPOSURE OF LIVE |
| PARTS. |
| 110.27,230.76,230.79 |
| |
| 2) NOTE: PLEASE SEE PREVIOUS COMMENT |
| WITH RESPECT TO LOAD ON GENERATOR, WHICH |
| RESPONSE MENTIONS TO SEE A DETAIL ON E-3 |
| FOR LOAD SHEDDING. |
| THIS IS OK AND IS PERMITTED, HOWEVER |
| DETAIL MENTIONS TO SEE E-6 FOR LOAD |
| SHEDDING , HOWEVERNO SYSTEM DETAIL OR |
| HOW THESE LOADS ARE BEING SHEDDED. |
| PLEASE INDICATE EQUIPMENT BEING |
| INSTALLED. |
| |
| 3) NOTE: PLEASE SEE PREVIOUS NOTE WHICH |
| REQUESTED REFERENCE TO NFPA-110 2002. |
| RESPONSE MENTIONS GEN DOES NOT FALL |
| UNDER NFPA-110. |
| PLEASE SEE FBC 2702.1 WHICH REQUIRES |
| "STAND-BY" SYSTEMS TO ALSO BE INSTALLED |
| PER NFPA-110. |
| |
| 4) NOTE: PLEASE SEE PREVIOUS COMMENT |
| WHICH REQUESTED TO INDICATE THE OCP AT |
| GENERATOR. PLEASE SEE RESPONSE MENTIONS |
| "SELF PROTECTED RELAY" ?? |
| PLEASE INDICATE THE OCP AT GEN. |
| 215.5 |
| |
| 5) NOTE: PLEASE SEE COMMENT ONE, WHICH |
| REQUESTED FOR VALUE FOR COMPLETE SCOPE |
| OF WORK TO BE UPDATED. THE RESPINSE |
| MENTIONS $137K, HOWEVER THIS WAS NOT |
| DONE WHEN PLANS WERE RESUBMITTED, |
| THEVALUE HAS SINCE BEEN INCREASED AND |
| FEES ARE DUEAND MUST BE PAID BEFORE |
| RESUBMITTING PLANS. |
| 108.3 FBC. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |