Plan Review Notes For Permit 06040063 |
Permit Number |
06040063 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-04-05 00:00:00 | DENIED: | | | | 1.PLEASE INDICATE DISTANCES TO | | OPENINGS AND ANY FRESH AIR INTAKES PER | | 2004 FMC 401.5.1. | | | | 2.PLEASE PROVIDE INFORMATION AND | | DETAIL FOR ANCHORING PER 2004 FMC | | 301.13. | | | | 3.PLEASE PROVIDE INFORMATION FOR THE | | FUEL OIL PIPING AND FILL PIPING.SHOW | | COMPLIANCE WITH NFPA 37, 54 AND 110. | | | | 4.PROVIDE CAPACITY OF THE FUEL STORAGE | | TANK. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. | | |
|