2006-04-05 00:00:00 | ***********UNSAT ************* |
| |
| 1) NOTE:PLEASE ADJUST VALUE FOR |
| COMPLETE SCOPE OF WORK BEING APPLIED |
| FOR. PLEASE KNOW, THAT VALUE SHALL BE |
| ALL LABOR AND MATERIALS EVEN IF |
| MATERIALS ARE OWNER SUPPLIED. PLEASE SEE |
| VALUE FOR LABOR AND INSTALLATION IS WAY |
| LOW FOR SCOPE PF WORK. PLEASE SEE FBC |
| 2004, ADMINISTRATIVE CODE SECTION 108.3 |
| AS ADOPTED BY THE CITY OF WEST PALM |
| BEACH. |
| |
| 2) NOTE: PLEASE SEE FLORIDA |
| ADMINISTRATIVE CODE 61G15-23.002 FOR |
| REQUIRED TITLE BLOCKS REQUIRED ON ALL |
| SAID SHEETS SIGNED, AND SEALED BY THE |
| ENGINEER OF RECORD. |
| TITLE BLOCKS ARE TO BE ON ALL SHEETS. |
| PLEASE KNOW, THIS COMMENTS IS FOR ALL |
| TRADES AND FOR ALL REVIEWS WHETHER OR |
| NOT COMMENT(S) ARE MADE BY OTHER |
| REVIEWER(S). |
| |
| 3) NOTE: PLEASE SEE SPECS SUBMITTED FOR |
| APS/ ATS DO NOT INDICATE THE REQUIRED |
| MEANS OF DISCONNECT AS REQUIRED BY |
| 230.76,230.79,225.31-39. |
| PLEASE SEE A MANUAL MEANS OF DISCONNECT |
| COULD NOT BE LOCATED RATED FOR THE LOAD |
| SERVED ON THE OUTSIDE OF EQUIPMENT |
| SUBMITTED. |
| |
| 4) NOTE: PLEASE CORRELATE SPECS/ |
| MANUFACTURES CUT SHEETS AND PLANS. |
| PLEASE SEE ONE SHOWS 3000A AND THE |
| 3200A'S, ARE THESE THE SAME?AS MANY |
| LOCATIONS ON PLANS MENTIONS 3000A'S. |
| 215.5 |
| |
| 5) NOTE: PLEASE CLARIFY WHY THE NEW MAIN |
| AND OCP52 MUT IS MENTIONED AS BEING |
| SET ABOVE EXISTING MAINS. PLEASE CLARIFY |
| AS THIS EQUIPMENT IS NOW BECOMING THE |
| NEW SERVICE MAIN(S) AND SHOULD BE |
| PROVIDING THE MAX OCP FOR EACH OF THE |
| EXISTING MAINS AND CONDUCTORS. |
| 215.5,240.4,,310.16 ETC |
| |
| 6) NOTE: PLEASE SEE LOADS PROVIDED ON |
| LOAD SUMMARY FROM THE 12 MONTH READING |
| INDICATES A LOAD HIGHER THAN THE MAX |
| RATING OD SAID GENERATOR. PLEASE PROVIDE |
| LOAD SHEDDING DETAIL FOR LOADS TO BE |
| SHEDDED AND THE NEW LOADS INTENDED ONCE |
| THE MININUM DE-RATING HAS TAKEN PLACE. |
| 215.5,702.5,220.35 |
| |
| 7) NOTE:PLEASE SEE PLANS SHALL |
| INDICATE THE CURRENT CODES IN EFFECT FOR |
| INSTALLATION AS FOLLOWS. |
| 2002 NFPA-70, 2002 NFPA-110. |
| |
| 8) NOTE: PLEASE SPECIFY IF GENERATOR IS |
| A SEPARATELY DERIVED SYSTEM OR NOT. |
| PLEASE SEE E-2 WHICH LENDS TO THE GEN |
| WINDINGS BEING TAPPED FOR NEW GROUNDING |
| ELECTRODE SYSTEM AND GROUNDING DETAIL ON |
| E-5 DOES NOT INDICATE AS A NEW GROUNDING |
| ELECTRODE SYSTEM. |
| THE SPEC FOR THE APS/ ATS DO NOT SEEM TO |
| INDICATE THE SWITCHING OF THE GROUNDED/ |
| NEUTRAL CONDUCTOR. |
| 250.30, 250.24 ETC. |
| |
| 9) NOTE: PLEASE SEE THE APS/ATS IS |
| BECOMING THE NEW FIRST MEANS OF |
| DISCONNECT HOWEVER THE NEW GROUNDING |
| ELECTRODE SYSTEMS DOE NOTE SEEM TO |
| COMPLETE AS PER 250.50. |
| PLEASE SEE GROUNDING DETAIL MENTIONS NEW |
| SLAB STEEL WHICH IS OK, HOWEVER DOES NOT |
| INDICATE A MIN OF 20' IN DIRECT CONTACT |
| WITH THE EARTH. |
| PLEASE KNOW, THE SLABS BEING POURED AS |
| MENTIONED TO THIS OFFICE ARE BEING |
| INSTALLED OVE RTHE EXISTING SITE |
| SLAB/CONCRETE PARKING/ BACK OF BLDG |
| AREA. |
| THESE NEW SLAB/STEEL ATTACHMENTS DO NOT |
| MEET THE MIN REQUIREMENTS. PER |
| 250.50,250.52, 250.104 |
| IF SLAB STEEL IS ONLY BEING BONDED , |
| THEN PLEASE INDICATE. |
| PLEASE COMPLETE GROUNDING ELECTRODE |
| SYSTEM(S) AND BONDING FOR ALL AS ABOVE. |
| |
| 10) NOTE: PLEASE SEE FEEDER CONDUITS, |
| NEW AND EXISTING. THERE IS NOW A CHANGE |
| IN CONDUCTOR SIZES FORTHE GROUNDED |
| NEUTRAL CONDUCTOR. PLEASE PROVIDE LOAD |
| CALCS FOR NEW DOWN SIZING OR INSTALL AS |
| SHOWN ON ORIG WITH FULL SIZE NEUTRAL. |
| 220.22, 215.5 |
| |
| 11) NOTE: PLEASE CORRELATE ALL CONDUITS, |
| FEEDERS AND SERVICE ENTRANCE CONDUITS. |
| PLEASE SEE THE NUMBER OF CONDUITS FOR 6A |
| AND 6B ARE DIFFERENET ON MORE THAN ONE |
| SHEET. PLEASE SEE 6A IS SHOWN AS 5 |
| SETS,6 SETS AND 7 SETS, AS WELL AS 6B |
| BEING SHOWN AS 4 SETS AND 6 SETS. |
| PLEASE VERIFY ALL OF THESE AS IT DOES |
| SEEM THAT THE NUMBER OF CONDUITS TO THE |
| EXISTING SERVICE WOULD BE INCREASED. |
| 215.5 |
| |
| 12) NOTE: PLEASE SEE SETS OF CONDUITS |
| AND FEEDERS DOD NOT SEEM TO INDICATE |
| THEW NEW REQUIRED "EQUIPMENT GROUNDING |
| CONDUCTOR" TO TEH EXISITING MAINS. THESE |
| ARE NO LONGER THE FIRST MENAS OF |
| DISCONNECT AND THE GROUNDING |
| DETAIL/RISER ON E-5 MENTIONS THE |
| DISCONNECT OF THE BONDING JUMPER, |
| HOWEVER THE CONDUITS/FEEDERS DONOT |
| SHOW THE EQUIPMENT GROUNDING CONDUCTORS |
| PER 250.110,250.122,250.24B |
| 215.5 |
| |
| 13) NOTE: PLEASE INDICATE OCP AT |
| GENERATOR. PLEASE ALSO SEE 445.13 FOR |
| MIN SIZING WHICH MAY BE AFFECTED. |
| CONDUCTORS AT 115%? |
| |
| 14) NOTE: PLEASE SEE LEGEND ON E-3 WHICH |
| MENTIONS THE "PINK HIGH-LIGHTED LINES" |
| AS WIRING BY OTHERS", HOWEVER PLEASE SEE |
| 4.1 WHICH SHOWS THIS SAME HIGH-LIGHTED |
| LINE AS A FENCE BY OTHERS? |
| 215.5 |
| |
| 15) NOTE: PLEASE SEE NOTE #4 ON E-1, |
| WHICH MENTIONS "STANDY" MODE, THIS SEEMS |
| TO BE A MISPRINT FOR THE INTENDED |
| "STAND-BY" MODE". |
| 215.5 |
| |
| 16) NOTE:PLEASE SUBMIT A MIN OF TWO |
| COPIES FOR ALL PLANS SPECS. IF THREE ARE |
| DESIRED TO BE STAMPED, PLEASE SUBMIT |
| THREE COMPLETE SETS. |
| PLEASE BE SURE TO REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO THE COMPLETED SETS FOR |
| REVIEW AND STAMPING BEFORE RESUBMITTING. |
| PLANS. |
| |
| 17) NOTE: PLEASE KNOW, IT IS KNOWN TO |
| THIS OFFICE THAT THERE IS AN EXISTING |
| GENERATOR AT THIS STORE LOCATION, |
| HOWEVER NO INFORMATION FOR THIS IS |
| INDICATED. PLEASE SHOW LOCATION AND HOW |
| THIS SYSTEM IS OR IS NOT TIED INTO THE |
| NEW SERVICE. |
| 215.5 |
| |
| 18) NOTE: PLEASE PROVIDE THE GPH USEAGE |
| OF GENERATOR FOR LOADS INTENDED. PLEASE |
| KNOW, A 1000 GAL TANK IS BEING SHOWN, |
| WHICH LENDS TO LESS THAN 24HRS OF |
| OPERTATION? IS THIS CORRECT? |
| THIS IS ONLY A NOTE,AS AN OPTIONAL |
| STAND-BY LEVEL 2 SYSTEMS DOES NOT |
| REQUIRED ANY MIN HRS OF OPERATION. |
| |
| |
| *** PLEASE SEE ANY COMMENTS FROM OTHER |
| TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| ** PLEASE SUBMIT THE ABOVE INFORMATION |
| FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |