Plan Review Notes
Plan Review Notes For Permit 06040063
Permit Number 06040063
Review Stop E
Sequence Number 1
Notes
Date Text
2006-04-05 00:00:00***********UNSAT *************
  
 1) NOTE:PLEASE ADJUST VALUE FOR
 COMPLETE SCOPE OF WORK BEING APPLIED
 FOR. PLEASE KNOW, THAT VALUE SHALL BE
 ALL LABOR AND MATERIALS EVEN IF
 MATERIALS ARE OWNER SUPPLIED. PLEASE SEE
 VALUE FOR LABOR AND INSTALLATION IS WAY
 LOW FOR SCOPE PF WORK. PLEASE SEE FBC
 2004, ADMINISTRATIVE CODE SECTION 108.3
 AS ADOPTED BY THE CITY OF WEST PALM
 BEACH.
  
 2) NOTE: PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 FOR
 REQUIRED TITLE BLOCKS REQUIRED ON ALL
 SAID SHEETS SIGNED, AND SEALED BY THE
 ENGINEER OF RECORD.
 TITLE BLOCKS ARE TO BE ON ALL SHEETS.
 PLEASE KNOW, THIS COMMENTS IS FOR ALL
 TRADES AND FOR ALL REVIEWS WHETHER OR
 NOT COMMENT(S) ARE MADE BY OTHER
 REVIEWER(S).
  
 3) NOTE: PLEASE SEE SPECS SUBMITTED FOR
 APS/ ATS DO NOT INDICATE THE REQUIRED
 MEANS OF DISCONNECT AS REQUIRED BY
 230.76,230.79,225.31-39.
 PLEASE SEE A MANUAL MEANS OF DISCONNECT
 COULD NOT BE LOCATED RATED FOR THE LOAD
 SERVED ON THE OUTSIDE OF EQUIPMENT
 SUBMITTED.
  
 4) NOTE: PLEASE CORRELATE SPECS/
 MANUFACTURES CUT SHEETS AND PLANS.
 PLEASE SEE ONE SHOWS 3000A AND THE
 3200A'S, ARE THESE THE SAME?AS MANY
 LOCATIONS ON PLANS MENTIONS 3000A'S.
 215.5
  
 5) NOTE: PLEASE CLARIFY WHY THE NEW MAIN
 AND OCP52 MUT IS MENTIONED AS BEING
 SET ABOVE EXISTING MAINS. PLEASE CLARIFY
 AS THIS EQUIPMENT IS NOW BECOMING THE
 NEW SERVICE MAIN(S) AND SHOULD BE
 PROVIDING THE MAX OCP FOR EACH OF THE
 EXISTING MAINS AND CONDUCTORS.
 215.5,240.4,,310.16 ETC
  
 6) NOTE: PLEASE SEE LOADS PROVIDED ON
 LOAD SUMMARY FROM THE 12 MONTH READING
 INDICATES A LOAD HIGHER THAN THE MAX
 RATING OD SAID GENERATOR. PLEASE PROVIDE
 LOAD SHEDDING DETAIL FOR LOADS TO BE
 SHEDDED AND THE NEW LOADS INTENDED ONCE
 THE MININUM DE-RATING HAS TAKEN PLACE.
 215.5,702.5,220.35
  
 7) NOTE:PLEASE SEE PLANS SHALL
 INDICATE THE CURRENT CODES IN EFFECT FOR
 INSTALLATION AS FOLLOWS.
 2002 NFPA-70, 2002 NFPA-110.
  
 8) NOTE: PLEASE SPECIFY IF GENERATOR IS
 A SEPARATELY DERIVED SYSTEM OR NOT.
 PLEASE SEE E-2 WHICH LENDS TO THE GEN
 WINDINGS BEING TAPPED FOR NEW GROUNDING
 ELECTRODE SYSTEM AND GROUNDING DETAIL ON
 E-5 DOES NOT INDICATE AS A NEW GROUNDING
 ELECTRODE SYSTEM.
 THE SPEC FOR THE APS/ ATS DO NOT SEEM TO
 INDICATE THE SWITCHING OF THE GROUNDED/
 NEUTRAL CONDUCTOR.
 250.30, 250.24 ETC.
  
 9) NOTE: PLEASE SEE THE APS/ATS IS
 BECOMING THE NEW FIRST MEANS OF
 DISCONNECT HOWEVER THE NEW GROUNDING
 ELECTRODE SYSTEMS DOE NOTE SEEM TO
 COMPLETE AS PER 250.50.
 PLEASE SEE GROUNDING DETAIL MENTIONS NEW
 SLAB STEEL WHICH IS OK, HOWEVER DOES NOT
 INDICATE A MIN OF 20' IN DIRECT CONTACT
 WITH THE EARTH.
 PLEASE KNOW, THE SLABS BEING POURED AS
 MENTIONED TO THIS OFFICE ARE BEING
 INSTALLED OVE RTHE EXISTING SITE
 SLAB/CONCRETE PARKING/ BACK OF BLDG
 AREA.
 THESE NEW SLAB/STEEL ATTACHMENTS DO NOT
 MEET THE MIN REQUIREMENTS. PER
 250.50,250.52, 250.104
 IF SLAB STEEL IS ONLY BEING BONDED ,
 THEN PLEASE INDICATE.
 PLEASE COMPLETE GROUNDING ELECTRODE
 SYSTEM(S) AND BONDING FOR ALL AS ABOVE.
  
 10) NOTE: PLEASE SEE FEEDER CONDUITS,
 NEW AND EXISTING. THERE IS NOW A CHANGE
 IN CONDUCTOR SIZES FORTHE GROUNDED
 NEUTRAL CONDUCTOR. PLEASE PROVIDE LOAD
 CALCS FOR NEW DOWN SIZING OR INSTALL AS
 SHOWN ON ORIG WITH FULL SIZE NEUTRAL.
 220.22, 215.5
  
 11) NOTE: PLEASE CORRELATE ALL CONDUITS,
 FEEDERS AND SERVICE ENTRANCE CONDUITS.
 PLEASE SEE THE NUMBER OF CONDUITS FOR 6A
 AND 6B ARE DIFFERENET ON MORE THAN ONE
 SHEET. PLEASE SEE 6A IS SHOWN AS 5
 SETS,6 SETS AND 7 SETS, AS WELL AS 6B
 BEING SHOWN AS 4 SETS AND 6 SETS.
 PLEASE VERIFY ALL OF THESE AS IT DOES
 SEEM THAT THE NUMBER OF CONDUITS TO THE
 EXISTING SERVICE WOULD BE INCREASED.
 215.5
  
 12) NOTE: PLEASE SEE SETS OF CONDUITS
 AND FEEDERS DOD NOT SEEM TO INDICATE
 THEW NEW REQUIRED "EQUIPMENT GROUNDING
 CONDUCTOR" TO TEH EXISITING MAINS. THESE
 ARE NO LONGER THE FIRST MENAS OF
 DISCONNECT AND THE GROUNDING
 DETAIL/RISER ON E-5 MENTIONS THE
 DISCONNECT OF THE BONDING JUMPER,
 HOWEVER THE CONDUITS/FEEDERS DONOT
 SHOW THE EQUIPMENT GROUNDING CONDUCTORS
 PER 250.110,250.122,250.24B
 215.5
  
 13) NOTE: PLEASE INDICATE OCP AT
 GENERATOR. PLEASE ALSO SEE 445.13 FOR
 MIN SIZING WHICH MAY BE AFFECTED.
 CONDUCTORS AT 115%?
  
 14) NOTE: PLEASE SEE LEGEND ON E-3 WHICH
 MENTIONS THE "PINK HIGH-LIGHTED LINES"
 AS WIRING BY OTHERS", HOWEVER PLEASE SEE
 4.1 WHICH SHOWS THIS SAME HIGH-LIGHTED
 LINE AS A FENCE BY OTHERS?
 215.5
  
 15) NOTE: PLEASE SEE NOTE #4 ON E-1,
 WHICH MENTIONS "STANDY" MODE, THIS SEEMS
 TO BE A MISPRINT FOR THE INTENDED
 "STAND-BY" MODE".
 215.5
  
 16) NOTE:PLEASE SUBMIT A MIN OF TWO
 COPIES FOR ALL PLANS SPECS. IF THREE ARE
 DESIRED TO BE STAMPED, PLEASE SUBMIT
 THREE COMPLETE SETS.
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO THE COMPLETED SETS FOR
 REVIEW AND STAMPING BEFORE RESUBMITTING.
 PLANS.
  
 17) NOTE: PLEASE KNOW, IT IS KNOWN TO
 THIS OFFICE THAT THERE IS AN EXISTING
 GENERATOR AT THIS STORE LOCATION,
 HOWEVER NO INFORMATION FOR THIS IS
 INDICATED. PLEASE SHOW LOCATION AND HOW
 THIS SYSTEM IS OR IS NOT TIED INTO THE
 NEW SERVICE.
 215.5
  
 18) NOTE: PLEASE PROVIDE THE GPH USEAGE
 OF GENERATOR FOR LOADS INTENDED. PLEASE
 KNOW, A 1000 GAL TANK IS BEING SHOWN,
 WHICH LENDS TO LESS THAN 24HRS OF
 OPERTATION? IS THIS CORRECT?
 THIS IS ONLY A NOTE,AS AN OPTIONAL
 STAND-BY LEVEL 2 SYSTEMS DOES NOT
 REQUIRED ANY MIN HRS OF OPERATION.
  
  
 *** PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]