2006-08-16 00:00:00PROVISO: THESE PROBLEMS NEED TO BE FIXED
 BEFORE FINAL OR NO POWER WILLL BE
 RELEASED TO THE BUILDINGS.JLEAHY
  
  
 RISER DIAGRAM ONLY SHOWS 2/0 WIRE IF THE
 LOAD CALCULATION FOR THE UNITS IS A 138
 EACH THEN THE 2/0S ARE TOO SMALL. PLEASE
 RESUBMIT NEW CLACULATIONS OR A NEW RISER
 DIAGRAM.
  
 ON PAGE 4-7 RISER SHOWS TWO 200A AMIN
 ACCORDING TO THE NOTES IN THE PANEL
 SCHEDULE, BUT ON THE BUILDING YOU SHOW 1
 AT 200 AND 1 AT 150????? PLEASE FIX
 BEFORE FINAL ELECTRICAL INSPECTION.
  
 PAGE 5-7 RISER SHOWS 200AMP MAIN, PANEL
 SCHEDULR SHOWS 150AMP MAIN. PLEASE FIX
 BEFORE FINAL INSPECTION.
  
 NEED THE PERSON WHO HAS DRAWN THESE TO
 SIGN AND DATE THESE PLANS FOR THE ELEC.
  
 THESE ARE THE SAME COMMENTS THAT WHERE
 GIVEN TO YOU ON 8/19 PLEASE FIX OR YOU
 WILL NOT GET POWER TO THE UNITS/OR HAVE
 POWER SHUT OFF TO THE UNITS!!!!!!!!!!