Notes |
Date |
Text |
2006-06-14 00:00:00 | PAGE 5-7 | | | | RISER SHOWS TWO MAINS OFF ONE RISER | | WIRE IS GOOD FOR 200A, HOW IS SECOND | | METER FED? | | | | NO PANEL SCHEDULE SHOWN FOR SECOND | | PANEL.NO LOAD CALCULATION SHOWN FOR | | THE SPACE INVOLVED!!!!!!!!! | | | | NO LOAD CALCULATION FOR BOTH UNITS SHOWN | | PER NEC. | | | | YOU HAVE TWO PAGES 5-7 PLEASE CHANGE ONE | | OR YOU WILL FAIL AGAIN. | | | | IF STORAGE UNIT IS FOR BOTH TENANTS YOU | | NEED A SEPARATE METER AND PANEL FOR THAT | | ROOM!!!! | | | | CHECK YOUR LOAD CALCULATIONS SHOW THAT | | BOTH UNITS ARE 1200 SQFT??????????????? | | | | NEED THE PERSON WHO DESIGNED THIS PLAN | | TO SIGN IT AND DATE IT. |
|