Plan Review Notes
Plan Review Notes For Permit 06040040
Permit Number 06040040
Review Stop E
Sequence Number 2
Notes
Date Text
2006-06-14 00:00:00PAGE 5-7
  
 RISER SHOWS TWO MAINS OFF ONE RISER
 WIRE IS GOOD FOR 200A, HOW IS SECOND
 METER FED?
  
 NO PANEL SCHEDULE SHOWN FOR SECOND
 PANEL.NO LOAD CALCULATION SHOWN FOR
 THE SPACE INVOLVED!!!!!!!!!
  
 NO LOAD CALCULATION FOR BOTH UNITS SHOWN
 PER NEC.
  
 YOU HAVE TWO PAGES 5-7 PLEASE CHANGE ONE
 OR YOU WILL FAIL AGAIN.
  
 IF STORAGE UNIT IS FOR BOTH TENANTS YOU
 NEED A SEPARATE METER AND PANEL FOR THAT
 ROOM!!!!
  
 CHECK YOUR LOAD CALCULATIONS SHOW THAT
 BOTH UNITS ARE 1200 SQFT???????????????
  
 NEED THE PERSON WHO DESIGNED THIS PLAN
 TO SIGN IT AND DATE IT.