2006-04-11 00:00:00DENIED;
 1.SANITARY RISER DIAGRAM AND FLAT
 DRAWING DO NOT MATCH;
 A.FIRST FLOOR TUB AND SHOWER ARE
  
 NOT VENTED.
 B.FLAT DRAWING, SECOND FLOOR BATH-
 ROOM SHOWER IS NOT VENTED.
 C. KITCHEN SINK SHOULD BE DOWN
 STREAM OF BATHROOM GROUP SEC.
 909.1
 D. RISER DIAGRAM DOES NOT MATCH
 FLOOR PLAN.
 2. PLANS ARE BEING REVIEW UNDER THE
 FBC-2004 EDITION NOT 2001 PLEASE CHANGE
 NOTES.