Plan Review Notes
Plan Review Notes For Permit 06040040
Permit Number 06040040
Review Stop M
Sequence Number 1
Notes
Date Text
2006-04-10 00:00:00*** DENIED ***
 1) ENERGY CAL'S. NEED TO BE SIGNED BY
 PREPARER AND OWNER/AGENT.
  
 2) ENERGY CAL'S. ARE CALLING FOR A/C #2
 TO HAVE 5 KW HEAT, ELECT. AND MECH.
 PLANS ARE CALLING FOR 8 KW HEAT, PLEASE
 CORRECT.
  
 3) SHOW ON MECH. PLANS HOW AHU #2 IS
 GETTING ITS RETURN AIR AND ACCESS FOR
 SERVICE.
  
 4) SHOW ON MECH. PLANS LOCATION OF
 CONDENSER UNIT #2.
  
 5) BOLTH A/C SYSTEMS ARE LISTED AS #1 ON
 MECH. PLANS, PLEASE CORRECT.
  
 6) WHITE OUT CAN NOT BE USED ON PLANS
 PLEASE SUBMIT CORRECTED PLANS WITH OUT
 (WHITE OUT) ON THEM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.