Plan Review Notes For Permit 06040040 |
Permit Number |
06040040 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-04-10 00:00:00 | *** DENIED *** | | 1) ENERGY CAL'S. NEED TO BE SIGNED BY | | PREPARER AND OWNER/AGENT. | | | | 2) ENERGY CAL'S. ARE CALLING FOR A/C #2 | | TO HAVE 5 KW HEAT, ELECT. AND MECH. | | PLANS ARE CALLING FOR 8 KW HEAT, PLEASE | | CORRECT. | | | | 3) SHOW ON MECH. PLANS HOW AHU #2 IS | | GETTING ITS RETURN AIR AND ACCESS FOR | | SERVICE. | | | | 4) SHOW ON MECH. PLANS LOCATION OF | | CONDENSER UNIT #2. | | | | 5) BOLTH A/C SYSTEMS ARE LISTED AS #1 ON | | MECH. PLANS, PLEASE CORRECT. | | | | 6) WHITE OUT CAN NOT BE USED ON PLANS | | PLEASE SUBMIT CORRECTED PLANS WITH OUT | | (WHITE OUT) ON THEM. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|