2006-07-12 00:00:00 | ******REVISION DENIED****** |
| REFERENCE: FBC-2004 SEC. 424.2 OR |
| FBC-2004 RESIDENTIAL SEC. R4101 SWIMMING |
| POOLS: |
| |
| THE FOLLOWING INFORMATION IS REQUIRED |
| FOR PLUMBING PLAN REVIEW: |
| |
| 1. THE REVISED PRINTS INDCATE A HEATER |
| TO BE INSTALLED BY OTHERS ON THE POOL |
| SPECIFICATIONS AND IS ALSO SHOWN ON THE |
| PIPING SCHEMATIC BUT THE PERMITTED SET |
| DOES NOT HAVE A HEATER INDICATED OR |
| APPROVED. PLEASE PROVIDE THE FOLLOWING |
| INFORMATION ON THE HEATER FOR THE |
| REVISED PRINTS OR DELETE HEATER ON |
| REVISION RESUBMITTAL. |
| 2. FBC-2004 SEC. 424.2.14.1, OR |
| FBCR-2004 SEC. R4101.14.1 SWIMMING POOL |
| WATER HEATERS SHALL BEAR THE LABEL OF A |
| RECOGNIZED TESTING AGENCY. (MANUFACTURE |
| SHEETS REQUIRED, PLEASE SUBMIT) |
| 3. FBC-2004 SEC. 424.2.14.2, OR |
| FBCR-2004 SEC. R4101.14.2 WATER |
| RETENTION, PROVIDE A POSITIVE MEANS OF |
| RETAINING WATER IN THE HEATER WHEN PUMP |
| IS SHUT OFF.(MANUFACTURE SHEETS |
| REQUIRED, PLEASE SUBMIT) |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| |
| END OF COMMENTS: |
| |