Plan Review Notes For Permit 06040012 |
Permit Number |
06040012 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-04-12 00:00:00 | ******DENIED****** | | REFERENCE: FBC-2004 424.2 SWIMMING POOLS | | | | PLEASE ADJUST YOUR NOTES, DETAILS, OR | | SUMMITTALS TO REFLECT THE FOLLOWING | | INFORMATION REQUIRED FOR PLAN REVIEW. | | | | 1. PLEASE CORRELATE THE EQUIPMENT LAYOUT | | WITH THE LEGEND. | | 2. PRINT INDICATES A 5 TON ELECTRIC HEAT | | PUMP. THE MANUFACTURER'S SUBMITTAL IS A | | GAS HEATER. PLEASE CORRELATE THE | | MANUFACTURER SUBMITTAL WITH THE PRINT. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 |
|