2006-04-11 00:00:00********** UNSAT ************
  
 1) NOTE: PLEASE CORRELATE ELECTRICAL
 PLANS WITH LOAD CALCUALTIONS SUBMITTED.
 PLEASE SEE PLANS INDICATE THREE LTS.
 215.5
  
 2) NOTE: PLEASE COMPLETE MIN WIRING ON
 ELECTRICAL WIRING DIAGRAM FOR EQUIPMENT.
 PLEASE SEE PUMP, HEATER, ETC DO NOT
 INDICATE ANY SIZES ETC.
 240.4,310.16,215.5
  
 3) NOTE: PLEASE SEE SPECS SUBMITTED FOR
 POOL HEATERARE FOR A GAS HEATER AND
 PLANS MENTIONS AN ELECTRICAL HEAT PUMP?
 PLEASE ADJUST PLANS,OR LOADS AND PANEL
 SCHEDULE ACCORDINGLY.
 PLEASE SUBMIT SPECS FOR THE HEAT PUMP
 BEING INSTALLED IN THIS HOUSE AND FOR
 THIS JOB. SPECS AND CALCS SHALL NOT BE
 GENERIC AS THE CODE REQUIRES EACH
 JOBSITE SCOPE TO BE SPECIFIC.
 ALL SPECS SHALL INDICATE A NRTL.
 215.5
  
 4) NOTE: PLEASE SEE HEATER AS LISTED ON
 PANEL SCHEDULE SHOWS 2-POLE 60A ON#8.
 PLEASE SEE 240.4,310.16,240.6, AS THIS
 MUST BE # 6 AWG OR LARGER.
  
 5) NOTE: PLEASE INDICATE ALL CONTINUOUS
 LOADS AT 125%. LOADS ONLY SHOWTHE
 LARGEST MOTOR LOAD AT 125%.
 PLEASE KNOW THE HEAT PUMP WILL RUN 3 OR
 MORE HRS AND WILL BE CONSIDERED
 CONTINUOUS. 215.3,230.42
  
 6) NOTE: PLEASE SEE PLANS MISSING THE
 REQUIRED EQUIPMENT GROUNDING CONDUCTOR
 FEEDING NEW SUB PANEL.
  
 7) NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR THE EXISTING SERVICE AND THE
 ADDITION OF THE NEW LOADS. PLEASE SEE
 ONLY THE LOADS FOR THE NEW SUB PANEL
 WERE SUBMITTED AND NO INFORMATION FOR
 SIZE AND EXISTING PANEL/SERVICE LOAD WAS
 GIVEN.
 220.31B,215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  