2006-04-11 00:00:00 | ********** UNSAT ************ |
| |
| 1) NOTE: PLEASE CORRELATE ELECTRICAL |
| PLANS WITH LOAD CALCUALTIONS SUBMITTED. |
| PLEASE SEE PLANS INDICATE THREE LTS. |
| 215.5 |
| |
| 2) NOTE: PLEASE COMPLETE MIN WIRING ON |
| ELECTRICAL WIRING DIAGRAM FOR EQUIPMENT. |
| PLEASE SEE PUMP, HEATER, ETC DO NOT |
| INDICATE ANY SIZES ETC. |
| 240.4,310.16,215.5 |
| |
| 3) NOTE: PLEASE SEE SPECS SUBMITTED FOR |
| POOL HEATERARE FOR A GAS HEATER AND |
| PLANS MENTIONS AN ELECTRICAL HEAT PUMP? |
| PLEASE ADJUST PLANS,OR LOADS AND PANEL |
| SCHEDULE ACCORDINGLY. |
| PLEASE SUBMIT SPECS FOR THE HEAT PUMP |
| BEING INSTALLED IN THIS HOUSE AND FOR |
| THIS JOB. SPECS AND CALCS SHALL NOT BE |
| GENERIC AS THE CODE REQUIRES EACH |
| JOBSITE SCOPE TO BE SPECIFIC. |
| ALL SPECS SHALL INDICATE A NRTL. |
| 215.5 |
| |
| 4) NOTE: PLEASE SEE HEATER AS LISTED ON |
| PANEL SCHEDULE SHOWS 2-POLE 60A ON#8. |
| PLEASE SEE 240.4,310.16,240.6, AS THIS |
| MUST BE # 6 AWG OR LARGER. |
| |
| 5) NOTE: PLEASE INDICATE ALL CONTINUOUS |
| LOADS AT 125%. LOADS ONLY SHOWTHE |
| LARGEST MOTOR LOAD AT 125%. |
| PLEASE KNOW THE HEAT PUMP WILL RUN 3 OR |
| MORE HRS AND WILL BE CONSIDERED |
| CONTINUOUS. 215.3,230.42 |
| |
| 6) NOTE: PLEASE SEE PLANS MISSING THE |
| REQUIRED EQUIPMENT GROUNDING CONDUCTOR |
| FEEDING NEW SUB PANEL. |
| |
| 7) NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| FOR THE EXISTING SERVICE AND THE |
| ADDITION OF THE NEW LOADS. PLEASE SEE |
| ONLY THE LOADS FOR THE NEW SUB PANEL |
| WERE SUBMITTED AND NO INFORMATION FOR |
| SIZE AND EXISTING PANEL/SERVICE LOAD WAS |
| GIVEN. |
| 220.31B,215.5 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
| |