2006-04-12 00:00:00 | ******** UNSAT *********** |
| |
| 1) NOTE: PLEASE PROVIDE A SCHEDULE FOR |
| THE TRANSFER PANEL FOR INTENDED LOADS |
| AND PLEASE CLARIFY AHU LOAD. UNLESS |
| AUTOMATIC LOAD SHEDDING IS DETAILED AND |
| PROVIDED, AHU HEAT SHALL BE FIGURED AT |
| 100%. |
| 220, 702.5 |
| PLEASE KNOW, MANY OF THE PRE-WIRED |
| PANELS DO NOT CONTAIN THE OCP WHICH MAY |
| BE NEEDED FOR THE INTENDED LOADS AND |
| ALTERATION OF LISTED EQUIPMENT IS NOT |
| PERMITTED. |
| |
| 2) NOTE: PLEASE RE-DRAWN RISER WITH OUT |
| HAND DRAWN AND WHITE-OUT CHANGES. PLEASE |
| INCLUDE DISCONNECTING MEANS FROM |
| GENERATOR TO MAIN HOUSE AND THIS |
| DISCONNECTING MEANS SHALL BE GROUPED |
| WITH THE EXISTING MAIN. |
| 225.31-225.39. |
| |
| 3) NOTE: PLEASE INCLUDE LOCATIONS OF ALL |
| SERVICE EQUIPMENT AS SHOWN ON RISER ON |
| THE PROVIDED SITE LAYOUT. PLEASE SEE |
| PLANS, AT CURRENT TIME ONLY INDICATE THE |
| ATS ON THE OUTSIDE OF DWELLING. |
| 215.5 |
| |
| 4) NOTE: PLEASE SUBMIT SPECS FOR ATS/ |
| PANEL BEING INSTALLED. |
| PLEASE INDICATE THE AIC RAITNG FOR ATS. |
| NFPA-110, 6.5.2, NEC 110.9 |
| 215.5 |
| |
| 5) NOTE: PLEASE BE SURE ALL SHEETS |
| CONTAIN THE PRINTED NAME AND THE |
| SIGNATURE OF THE PERSON TAKING |
| RESPONSIBILITY FOR PLANS AND DESIGN. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW., IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |