 DENIED
  
 THE LOADS INDICATED AS "OPERATED AT
 OWNERS DISCRETION" ARE SUBJECT TO BE
 ENERGIZED WHEN THE ATS IS ENERGIZED.
 DISCRETIONARY LOADS ARE CONSIDERED ALL
 CIRCUITS IN ANY PANELS ENERGIZED BY AN
 AUTOMATIC SWITCH, SINCE THERE IS NO WAY
 OF KNOWING WHAT CIRCUITS MAY ENERGIZE IN
 THE OWNERS ABSCENCE.
 LOAD SHEDDING IS PERMISIBLE.
  