Plan Review Notes For Permit 06031477 |
Permit Number |
06031477 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-04-13 00:00:00 | | | DENIED | | | | THE LOADS INDICATED AS "OPERATED AT | | OWNERS DISCRETION" ARE SUBJECT TO BE | | ENERGIZED WHEN THE ATS IS ENERGIZED. | | DISCRETIONARY LOADS ARE CONSIDERED ALL | | CIRCUITS IN ANY PANELS ENERGIZED BY AN | | AUTOMATIC SWITCH, SINCE THERE IS NO WAY | | OF KNOWING WHAT CIRCUITS MAY ENERGIZE IN | | THE OWNERS ABSCENCE. | | LOAD SHEDDING IS PERMISIBLE. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|