Plan Review Notes
Plan Review Notes For Permit 06031430
Permit Number 06031430
Review Stop B
Sequence Number 1
Notes
Date Text
2006-04-27 00:00:00 
  
 DENIED
  
 1) PROVIDE CORRECT DESIGN CRITERIA,
 SHALL COMPLY WITH 2004 FBC AND
 APPLICABLE TABLES
  
 2) PROVIDE SITE PLAN AND ELEVATON OF
 BUILDING TO VERIFY COMPLIANCE WITH THE
 PROVISIONS OF SECTION 1022 FBC
  
 3) STAIR TREADS SND RISERS SHALL COMPLY
 WITH THE PROVISIONS OF 1009.3 AND
 11-4.9.2 FBC (MAX RISE 7" MIN RUN 11")
  
 4) DETAIL 2 SHOWS TREAD OF 11" WHILE THE
 ELEVATION SHOWS 9 7/8" PLEASE CLARIFY
  
 5) PROVIDE FOUNDATION DETAIL FOR NEW
 STEEL COLUMNS
  
 6) PROVIDE ADDITIONAL INFORMATION :
 OCCUPANCY TYPE FOR BOTH FLOORS, IS THIS
 THE ONLY MEANS OF EGRESS FOR 2ND FLOOR
  
 BLDG PLAN REVIEW