Plan Review Notes For Permit 06031343
Permit Number 06031343
Review Stop E
Sequence Number 1
Notes
Date Text
2006-04-03 00:00:00NEED RISER DIAGRAM. 215.5
  
 NEED PANEL SCHEDULE. 408.4
  
 NEED TO SHOW ARC FAULTS. 210.12
  
 NEED TO SHOW GFCI CIRCUITS. 210.8 (A)
  
 NEED OUTLETS ON FRONT AND BACK OF HOUSE.
 210.52 (E)
  
 IF YOU CAN FAX IT TO ME I WILL PUT WITH
 DRAWINGS.JLEAHY 644-7291 C, 805-6676 F