Plan Review Notes
Plan Review Notes For Permit 06031339
Permit Number 06031339
Review Stop B
Sequence Number 3
Notes
Date Text
2006-10-16 17:10:20BUILDING REVIEW THIRD CHECKLIST:
  
 ***NOTE:
 CAPITAL LETTERS REFLECT ORIGINAL COMMENTS. LOWER CASE
 LETTERS REFLECT COMMENTS TO SUBMITTAL PACKAGE.
  
 1- PROVIDE COMPLETE SET OF STRUCTURAL DRAWINGS SHOWING
 STRUCTURAL WORK TO BE PERFORMED WITH COMPLETE
 SPECIFICATIONS AND DETAILSTHAT COMPLY WITH SECTION
 1609 OF FBC 2004 AND EXISTING BUILDINGS 2004 CODE.
  
 *** NO DONE. STRUCTURAL DRAWINGS WERE NOT SUBMITTED.
 THERE IS NOT INFORMATION GIVEN FOR REPLACING FRAMING
 AND SIDING.
 ***THERE IS ONE DRAWING SUBMITTED, BUT IT DOESN'T HAVE
 ANY STRUCTURAL SPECIFICATION. IT ONLY SHOWS LOCATION OF
 SIDING AND WINDOWS AND DOORS TO BE REPLACED. THERE ARE
 NO DRAWINGS AND SPECS ADDRESING THE ISSUE OF REPLACING
 ROTTEN FRAMING. THE ONLY ADDITIONAL DRAWING SUBMITTED
 WAS FOR A TYPICAL BUCK INSTALLATION.
 ***NOTE: SEE HARDIBOARD PRODUCT APPROVAL TO VERIFY
 COMPLIANCE WITH THE INSTALLATION. CHECK STUDS SPACING,
 ETC.
  
 2- PROVIDE FLORIDA OR LOCAL PRODUCT APPROVAL FOR
 STRUCTURAL FRAMING CONNECTORS THAT WILL BE SPECIFIED ON
 THE STRUCTURAL DRAWINGS.
 ***NO DONE. THERE ARE NO STRUCTURAL DRAWINGS AND
 SPECS.
  
 3- PROVIDE FLORIDA OR LOCAL PRODUCT APPROVAL FOR SIDING
 TO BE INSTALLED AS REQUIRED BY RULE 9B-72 OF DCA. ***
 PRODUCT APPROVAL SUBMITTTED IS FOR HARDIBOARD. NEED
 ALSO THE PRODUCT APPROVAL FOR WOOD SIDING IN FRONT
 ELEVATION AS CALLED FOR IN THE SUBMITTED DRAWING.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITTING
 ALL PRODUCT APPROVALS PRIOR TO SUBMITTAL TO THIS OFFICE
 AS REQUIRED BY SEC. 106.3.3 OF CITY AMENDMENTS TO FBC
 2004.
 ***NO DONE.
  
 5- PROVIDE FLORIDA OR APPLY FOR LOCAL PRODUCT APPROVALS
 FOR ALL TYPE AND SIZE OF WINDOWS AND WINDOWS TO BE
 REPLACED AS REQUIRED BY RULE 9B-72 OF DEPARTMENT OF
 COMMUNITY AFFAIRS (DCA).
 *** PRODUCT APPROVAL APPLICATIONS NEED TO HAVE THE NAME
 AND SIGNATURE OF APPLICANT.
 ***APPLICATIONS FOR SITE SPECIFIC PRODUCT APPROVAL WILL
 BEFORWARDED TO ROBERT BROWN FOR REVIEW AND APPROVAL.
  
 6- PROVIDE KEY PLAN AND A COMPLETE INSTALLATION
 SCHEDULE FOR STORM SHUTTERS. SEE ATTACHED SAMPLE OF
 STORM SHUTTERS INSTALLATION SCHEDULE.
 ***NEED TO PROVIDE ALL INFORMATION ON INSTALLATION
 SCHEDULE. MISSING OPENINGS SIZES, ETC.
  
 7- PROVIDE STRUCTURAL BUCK DETAILS FOR DOORS AND
 WINDOWS AS REQUIRED BY SEC. 1714.5.4.2 FBC 2004. ***
 CLARIFY BUILDING TYPE OF CONSTRUCTION. TYPICAL BUCK
 DETAIL DONE BY FREDRICK D. SHAFFER, PE CALLS FOR
 ATTACHMENT OF BUCKS TO MASONRY CONSTRUCTION. IS THIS
 BUILDING A WOOD FRAMED BUILDING OR CONCRETE BLOCK
 CONSTRUCTION?.
 *** ENGINEER NEEDS TO PROVIDE ALL INFORMATION REQUIRED
 BY SEC. 1603.1.4 FBC 2004.
 *** ENGINEER TO PROVIDE HIS FIRM CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED BY FLORIDA
 ADMINISTRATIVE CODE SEC. 61G15-23.002. SEE ATTACHED
 COPY.
 *** ENGINEER TO PROVIDE DRAWINGS WITH ORIGINAL
 SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES.
  
 8- VALUATION OF PROJECT WILL BE EVALUATED AFTER
 COMPLETE SET OF DRAWINGS ARE SUBMITTED TO DEFINE
 SPECIFIC SCOPE OF WORK.
 ***NO DRAWINGS AND SPECS SHOWING PROPOSED SCOPE OF
 WORK.
  
 9- NEED TO PROVIDE 2 COPIES OF EVERYTHING INCLUDING
 DRAWINGS AND SHUTTERS INFORMATION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712