2006-03-29 00:00:00 | ROOF OVER APPLICATION SENT TO | | PRE-INSPECTION BOX. | | | | BUILDING REVIEW CHECKLIST: | | 1- ROOF OVER PERMITS REQUIRES | | PRE-INSPECTION. APLICATION WAS SENT TO | | THE PRE-INSPECTION BOX. | | | | 2- UNABLE TO VERIFY COMPLIANCE WITH THE | | CODE IF METAL ROOFING SYSTEM INFORMATION | | IS NOT PROVIDED. ONLY THE FLORIDA | | PRODUCT APPROVAL COVER PAGE WAS | | SUBMITTED. NEED TO PROVIDE THE | | CORRESPONDING INFORMATION THAT WAS | | SUBMITTED TO GET THE FLORIDA PRODUCT | | APPROVAL. VISIT THE WEBSITE | | WWW.FLORIDABUILDING.ORG TO DOWNLOAD THE | | SPECIFIC INFORMATION THAT WAS SUBMITTED | | TO GE THE FLORIDA APPROVAL. PROVIDE TWO | | COMPLETE COPIES. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|