Plan Review Notes
Plan Review Notes For Permit 06031290
Permit Number 06031290
Review Stop E
Sequence Number 1
Notes
Date Text
2006-04-12 00:00:00******UNSAT *********
  
  
 1) NOTE: PLEASE WHOW THE FOLLOWING
 CURRENT CODES FOR ELECTRICAL PLANS.
 2002 NFPA-70, 2002 NFPA-72.
  
 2) NOTE: PLEASE SEE MECH SHEETS/ PLANS
 COULD NOT BE LOACTED FOR COMPARISON OF
 EQUIPMENT ETC TO THE ENERGY CODE AND
 CORRELATION WITH ELECTRICAL PLANS.
 471.025
  
 3) NOTE: PLEASE SEE SEAL FOR ENGINEER
 WITH THE WORDING OF "CERTIFICATE" HAS
 EXPIRED FOR USE. PLEASE SEE FAC
 61G15-23.001, WHICH REQUIES THE SEAL TO
 INDICATE THE WORDING OF "LICENSE". THIS
 WAS PASSED IN FEB 04 AND AN EXTENSION
 WAS GRANTED TO THE DATE OF DEC 30TH,
 2005.
 SEAL IS TO BE UPADTED.
 ** PLEASE ALSO BE SURE ALL SEALS ARE
 RAISED, CLEAR AND VISABLE WIHT ALL
 INFORMATION ON SAID SAL. FS 471.025
  
 4) NOTE:PLEASE SEE NOTES FOR SCOPE PF
 WORK MENTIONS ALL NEW ELECTRICAL
 SERVICE, YET RISER MENTIONS EXISTING?
 PLEASE CORRELATE.
 IF NEW AND DUE TO THE SCOPE OF WORK AND
 LEVEL OF REPAIR AND ALTERATION UNDER FBC
 AND EXISTING DWELLINGS, IF CONDUIT TO
 MCB PANEL IS NOT IN SLAB FROM METER, A
 MAIN DISCONNECT CONTAINING OCP WILL BE
 REQUIRED LOCATED OUTSIDE BEFORE ENTERING
 DWELLING. PLEASE SEE 230.70
 PLEASE SHOW THE LOCATION OF THE METER
 AND PLEASE INDICATE IF FEED TO PANEL IS
 LOCATED UNDER GROUND.
  
 5) NOTE: PLEASE SEE A FEW MISSING
 RECEPTS PER 210.52. PLEASE SEE SPACING
 WITHIN 6' OF DOORS AND EVERY 12' THERE
 AFTER.
  
 6) NOTE: PLEASE KNOW, IF SERVICE IS NEW,
 PLEASE SUBMIT AIC RATINGS FOR ALL NEW.
 110.9,215.5
  
  
 7 NOTE: PLEASE SEE RISER MENTIONS TO
 TAKE THE GROUNDING ELECTRODE CONDUCTOR
 TO THE EXISTING FOUNDATION STEEL. PLEASE
 KNOW, IF THIS IS AN EXISTING BUILDING
 AND THE ATTACHMENT IS NOT THERE, THIS IS
 NOT REQUIRED BY THIS AHJ. IN FACT, THIS
 MAY INDEED AFFECT THE STRUCTURAL
 STRENGTH OF THE EXISTING FOOTING. THIS
 MAY BE DONE , HOWEVER THIS IS NOT
 REQUIRED,
 ** PLEASE KNOW, IF SHOWN ON PLANS/RISER
 THEN THIS WILL BE REQUIRED.
  
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT THE
 ELECTRICAL PLANS.
  
 *** BEFORE RESUBMITTING PLANS, PLEASE
 COMPLETELY REMOVED ALL OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO SETS FOR REVIEW AND
 STAMPIN.
 ONLY ONE COPY OF THE OLD/VOIDED REMOVED
 SHEETS SHOULD BE SUBMITTED FOR
 REFERENCE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  