2006-04-12 00:00:00 | ******UNSAT ********* |
| |
| |
| 1) NOTE: PLEASE WHOW THE FOLLOWING |
| CURRENT CODES FOR ELECTRICAL PLANS. |
| 2002 NFPA-70, 2002 NFPA-72. |
| |
| 2) NOTE: PLEASE SEE MECH SHEETS/ PLANS |
| COULD NOT BE LOACTED FOR COMPARISON OF |
| EQUIPMENT ETC TO THE ENERGY CODE AND |
| CORRELATION WITH ELECTRICAL PLANS. |
| 471.025 |
| |
| 3) NOTE: PLEASE SEE SEAL FOR ENGINEER |
| WITH THE WORDING OF "CERTIFICATE" HAS |
| EXPIRED FOR USE. PLEASE SEE FAC |
| 61G15-23.001, WHICH REQUIES THE SEAL TO |
| INDICATE THE WORDING OF "LICENSE". THIS |
| WAS PASSED IN FEB 04 AND AN EXTENSION |
| WAS GRANTED TO THE DATE OF DEC 30TH, |
| 2005. |
| SEAL IS TO BE UPADTED. |
| ** PLEASE ALSO BE SURE ALL SEALS ARE |
| RAISED, CLEAR AND VISABLE WIHT ALL |
| INFORMATION ON SAID SAL. FS 471.025 |
| |
| 4) NOTE:PLEASE SEE NOTES FOR SCOPE PF |
| WORK MENTIONS ALL NEW ELECTRICAL |
| SERVICE, YET RISER MENTIONS EXISTING? |
| PLEASE CORRELATE. |
| IF NEW AND DUE TO THE SCOPE OF WORK AND |
| LEVEL OF REPAIR AND ALTERATION UNDER FBC |
| AND EXISTING DWELLINGS, IF CONDUIT TO |
| MCB PANEL IS NOT IN SLAB FROM METER, A |
| MAIN DISCONNECT CONTAINING OCP WILL BE |
| REQUIRED LOCATED OUTSIDE BEFORE ENTERING |
| DWELLING. PLEASE SEE 230.70 |
| PLEASE SHOW THE LOCATION OF THE METER |
| AND PLEASE INDICATE IF FEED TO PANEL IS |
| LOCATED UNDER GROUND. |
| |
| 5) NOTE: PLEASE SEE A FEW MISSING |
| RECEPTS PER 210.52. PLEASE SEE SPACING |
| WITHIN 6' OF DOORS AND EVERY 12' THERE |
| AFTER. |
| |
| 6) NOTE: PLEASE KNOW, IF SERVICE IS NEW, |
| PLEASE SUBMIT AIC RATINGS FOR ALL NEW. |
| 110.9,215.5 |
| |
| |
| 7 NOTE: PLEASE SEE RISER MENTIONS TO |
| TAKE THE GROUNDING ELECTRODE CONDUCTOR |
| TO THE EXISTING FOUNDATION STEEL. PLEASE |
| KNOW, IF THIS IS AN EXISTING BUILDING |
| AND THE ATTACHMENT IS NOT THERE, THIS IS |
| NOT REQUIRED BY THIS AHJ. IN FACT, THIS |
| MAY INDEED AFFECT THE STRUCTURAL |
| STRENGTH OF THE EXISTING FOOTING. THIS |
| MAY BE DONE , HOWEVER THIS IS NOT |
| REQUIRED, |
| ** PLEASE KNOW, IF SHOWN ON PLANS/RISER |
| THEN THIS WILL BE REQUIRED. |
| |
| |
| ** PLEASE SEE ANY OTHER COMMENTS FROM |
| OTHER TRADES WHICH MAY AFFECT THE |
| ELECTRICAL PLANS. |
| |
| *** BEFORE RESUBMITTING PLANS, PLEASE |
| COMPLETELY REMOVED ALL OLD/VOIDED SHEETS |
| FROM SETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO SETS FOR REVIEW AND |
| STAMPIN. |
| ONLY ONE COPY OF THE OLD/VOIDED REMOVED |
| SHEETS SHOULD BE SUBMITTED FOR |
| REFERENCE. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |