2006-03-28 00:00:00BUILDING REVIEW CHECKLIST:
 1- FLAT ROOF SYSTEM: A) ENGINEER TO
 REVIEW GENERAL LIMITATION #7 AND PROVIDE
 CALCULATIONS PER STANDARD RAS 117.
 B) ENGINEER TO REVIEW SPECIFIC PRODUCT
 APPROVAL SUBMITTED TO SEE FASTENER TYPE
 AND SPACING AND MAXIMUM DESIGN PRESSURES
 ALLOWED.
  
 2- SPECIFY HOW IS CONCRETE TILE FASTENED
 TO VERIFY COMPLIANCE WITH UPLIFT MOMENT.
 SCREWS OR NAILS AND HOW MANY.
 FOAM, PROVIDE PRODUCT APPROVAL.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER