Date |
Text |
2006-05-19 00:00:00 | RESPONSE TO ENGINEER'S FAX: |
| |
| 1- REGARDING THE SPECIFIC ASSEMBLY, |
| ENGINEER AND CONTRACTOR NEED TO |
| COORDINATE WHICH ASSEMBLY IS GOING TO BE |
| INSTALLED. ASSEMBLY SUBMITTED WAS FOR |
| INSULATED SYSTEM. NOW, ASSEMBLY |
| SUBMITTED IN ENGINEER'S FAX IS FOR A |
| NON-INSULATED ASSEMBLY. PLEASE PROVIDE |
| INFORMATION FOR ACTUAL ASSEMBLY THAT IS |
| GOING TO BE INSTALLED. |
| |
| 2- REGARDING THE BASE SHEET WIDTH, THE |
| NOA PRODUCT APPROVAL HAS THE DIMENSIONS. |
| PACKAGE SUMITTED CALLED FOR ELASTOBASE. |
| SEE PAGE 3 OF 45 OF THE NOA TO SEE THE |
| DIMENSIONS OF THE ELASTOBASE (65'-2" X |
| 3'-3 3/8"). |
| |
| 3- PROVIDE PRODUCT APPROVAL FOR |
| POLYGLASS BASE SHEET SHOWING THE |
| DIMENSIONS. SHEET FAXED SHOWING THE |
| POLYGLASS IS NOT THE PRODUCT APPROVAL. |
| IT'S MANUFACTURER'S LITERATURE, BUT IS |
| NOT THE APPROVED PRODUCT APPROVAL. |
| |
| 4- THE "0.08" VS ".8" IS NOT A |
| NITPICKING COMMENT. GO TO THE DADE |
| COUNTY NOA WEBSITE AND ENTER THE ".8" |
| AND SEE IF YOU CAN FIND THE INFORMATION. |
| THAT'S WHY CORRECT INFORMATION IS |
| IMPORTANT. |
| |
| 5- REGARDING FASTENER SPECIFICATIONS NOT |
| MATCHING, STILL DOESN'T MATCH. PAGE ONE |
| CALLS FOR 1 1/4" 11G WITH 1-5/8" TINTAG. |
| PAGE ONE OF CALCS CALLS FOR 1 1/4" 11G |
| WITH 1 3/4" TINTAG. |
| WHAT SIZE OF TINTAG IS IT? 1-5/8"? OR |
| 1-3/4"?. |
| CHECK THIS INFORMATION ALSO IN THE |
| FASTENER DIAGRAM SHEET. |
| |
| 6- ALL SHEETS NEED TO HAVE ENGINEER'S |
| SEAL, SIGNATURE AND DATE AS REQUIRED BY |
| CHAPTER 471 AND FAC.ENGINEER TO |
| CONTACT DEPARTMENT OF PROFESSIONAL |
| ENGINEER'S AT (850)521-0500 TO GET THEIR |
| INTERPRETATION ON THIS ISSUE. I CALLED |
| THEM SOME TIME AGO AND THEY TOLD ME ALL |
| SHEETS NEED TO BE SIGNED AND SEALED. |
| THAT'S WHY I AM ENFORCING THIS ISSUE. |
| I DIDN'T KNOW ENGINEER TALKED TO ROBERT |
| BROWN REGARDING THIS ISSUE. OTHERWISE, I |
| COULD INFORM HIM OF MY FINDINGS. |
| |
| 7- PLEASE PICK UP PACKAGE AND RE-SUBMIT |
| COMPLETE AND CORRECT PACKAGE. |
| RE-SUBMITTAL FEES APPLY. |
| |