2006-05-18 00:00:00BUILDING REVIEW SECOND CHECKLIST:
 1- ACCORDING TO THE DIMENSIONS GIVEN BY
 THE ENGINEER(L:25' AND W:24') TOTAL AREA
 IS 600SF. BUT PERMIT APPLICATION SAYS
 900SF. INFORMATION NEED TO MATCH. REVISE
 AS REQUIRED.
  
 2- ENGINEER TO CAREFULLY REVIEW SPECIFIC
 PRODUCT APPROVAL TO CORRECT THE
 FOLLOWING:
 A) CLEARLY IDENTIFY SPECIFIC ASSEMBLY
 FROM THE APPROVED ASSEMBLIES LISTED IN
 THE PRODUCT APPROVAL FOR WHICH THESE
 CALCULATIONS ARE DONE FOR.
 B) FASTENER TYPE DOESN'T MATCH
 FASTENER TYPE SHOWN ON THE PRODUCT
 APPROVAL.
 C) FASTENER SPACING AT SIDE LAP (8")
 FOR ZONE ONE DOESN'T MATCH FASTENER
 SPACING SHOWN ON PRODUCT APPROVAL (12").
 D) NOA NUMBER SPECIFIED ON FIRST SHEET
 DOESN'T MATCH NOA NUMBER SPECIFIED ON
 SHEET ONE OF CALCULATIONS. THERE ARE
 SIGNIFICANT DIFFERENCES BETWEEN THOSE
 TWO NOA'S.
 E) BASE SHEET WIDTH DIMENSION IS
 INCORRECT. SEE PRODUCT APPROVAL FOR
 CORRECT DIMENSION.
 F) DESIGN PRESSURES ON SHEET ONE OF
 CALCULATIONS DON'T MATCH THE DESIGN
 PRESSURES SHOWN ON NOA 03-0130.08.
 NOTE: ALSO, SEE CORRECT NOA NUMBER. LAST
 TWO DIGITS AFTER THE PERIOD ARE .O8, NOT
 .8.
 G) FASTENER SHOWN ON THE CALCULATION
 SHEET ONE DOESN'T MATCH FASTENER SHOWN
 ON FIRST PAGE OF ENGINEER'S REPORT.
 H) REVISE INFORMATION ON FASTENER
 DIAGRAM SHEET: FASTENER SPACING AT SIDE
 LAP FOR ZONE ONE AND CORRECT WIDTH
 DIMENSION FOR BASE SHEET.
 I) ENGINEER TO SIGN, SEAL AND DATE ALL
 FOUR PAGES AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE AND FAC 61G15-23.002.
  
 NOTE:
 ONE SET OF THE SUBMITTED PACKAGE WAS
 RETAINED IN THIS OFFICE TO SUBMIT TO THE
 BOARD OF PROFESSIONAL ENGINEERS FOR
 THEIR REVIEW.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.