Plan Review Notes
Plan Review Notes For Permit 06031268
Permit Number 06031268
Review Stop B
Sequence Number 1
Notes
Date Text
2006-05-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)SHEET A.0 DECLARES BUILDING TYPE AS
 1V.SEE FBC6, THIS SHOULD REFER TO A OR
 B.
  
 3.)DECLARE BUILDING SIZE, FBC5.
  
 4.)OCCUPANCY IS TO BE ONE IN CHAPTER
 3."PUMP HOUSE" IS NOT AN OCCUPANCY
 CLASSIFICATION.
  
 5.)PROVIDE FLOOD ZONE DESIGNATION.IF
 THIS IS LOCATED IN A HIGH HAZARD FLOOD
 ZONE, THE FINISHED FLOOR IS TO BE 6"
 ABOVE BFE, CITY OF WEST PALM BEACH
 MUNICIPAL CODE 94-546(B).IF THIS IS IN
 A HIGH HAZARD FLOOD ZONE, DECLARE BFE
 AND SHOW MINIMUM FFE ON THE PLAN.FORM
 BOARD WITH ELEVATIONS WILL BE REQUIRED.
  
 6.)ALL PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD
 FBC*106.3.3.
  
 7.)PROVIDE INSTALLATION INSTRUCTIONS
 FROM THE MANUFACTUER FOR THE SKYLIGHT.
  
 8.)THE FLORIDA STATE PRODUCT APPROVALS
 FOR THE CONNECTORS ARE EXPIRED, 2001
 CODE RATHER THAN 2004.
  
 9.)PROVIDE WIND DESIGN INFORMATION
 REQUIRED BY FBC1603.1.4.
  
 10.)SHUTTERS ARE REQUIRED FOR THE
 LOUVERED DOOR.SHUTTERS FOR COMMERCIAL
 BUILDINGS MUST BE APPROVED BY THE
 BUILDING OFFICIAL.SEE ATTACHED POLICY,
 ITEM 13.SUBMIT AN INSTALLATION PLAN.
 FAILURE TO ADDRESS THIS COMMENT WILL
 RESULT IN DELAYS IN PERMITTING.THE
 PLAN MAY BE SUBMITTED SEPARATELY FROM
 THE PERMIT RESUBMITTAL.
  
 11.)PROVIDE THE APPROVED ASSEMBLY YOU
 ARE USING FOR THE FLAT DECK.
  
 12.)THE SPEC SHEET FOR THE ROOF IS FOR
 A CONCRETE DECK, THIS IS WOOD.
  
 13.)THE SITE PLAN IS REQUIRED TO SHOW
 TABLE 601 COMPLIANCE.PROVIDE A SIGNED,
 SEALED, DATED SITE PLAN SHOWING DISTANCE
 TO EITHER THE PROPERTY LINE OR TO
 ADJACENT BUILDINGS AND ASSUMED PROPERTY
 LINES.
  
 14.)DOCUMENTS PREPARED BY A LANDSCAPE
 ARCHITECT ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS FS481.306.THE SITE
 PLAN PREPARED BY URBAN DESIGN DOES NOT
 SHOW THE PROPOSED IMPROVEMENT.SEE ALSO
 #13.
  
  