Plan Review Notes
Plan Review Notes For Permit 06031223
Permit Number 06031223
Review Stop B
Sequence Number 3
Notes
Date Text
2006-06-05 00:00:00DENIED
  
 1) SUBMIT THE ORIGINAL PERMIT
 APPLICATION AND NOTICE OF COMMENCEMENT.
  
 2) THE PRODUCT APPROVAL SUBMITTED FOR
 THE ROOFING MATERIAL DOES NOT MEET THE
 REQUIRED UPLIFT PRESSURE. THE PRODUCT
 APPROVAL FOR THE JOHNS MANVILLE SINGLE
 PLY ROOF SYSTEM LISTS MAXIMUM DESIGN
 PRESSURE AS -45 PSF WITH NO ENHANCED
 FASTENING ALLOWED. THE REQUIRED ROOF
 PRESSURES FROM TABLE 1609.6B ARE -59.2
 AT PERIMETER AREAS AND -89.0 AT THE
 CORNERS. SUBMIT PRODUCT APPROVAL FOR
 ROOFING MATERIAL THAT HAS ADEQUATE
 DESIGN PRESSURES. SEE COMMENT #4 ON LAST
 REVIEW.
  
 3) FBC 11-4.5.1 REQUIRES CHANGES IN
 LEVEL ON AN ACCESSIBLE ROUTE GREATER
 THAN 1/2 INCH SHALL BE ACCOMPLISHED BY
 MEANS OF A RAMP THAT COMPLIES WITH
 SECTION 11-4.7 OR 11-4.8. SPECIFY THE
 LOCATION OF RAMPS ON THE ACCESSIBLE
 ROUTES TO THE OFFICES. SPECIFY THE SLOPE
 OF THE RAMPS, ETC. COMMENT #7 ON LAST
 REVIEW.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714