Plan Review Notes For Permit 06031223 |
Permit Number |
06031223 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-06-05 00:00:00 | DENIED | | | | 1) SUBMIT THE ORIGINAL PERMIT | | APPLICATION AND NOTICE OF COMMENCEMENT. | | | | 2) THE PRODUCT APPROVAL SUBMITTED FOR | | THE ROOFING MATERIAL DOES NOT MEET THE | | REQUIRED UPLIFT PRESSURE. THE PRODUCT | | APPROVAL FOR THE JOHNS MANVILLE SINGLE | | PLY ROOF SYSTEM LISTS MAXIMUM DESIGN | | PRESSURE AS -45 PSF WITH NO ENHANCED | | FASTENING ALLOWED. THE REQUIRED ROOF | | PRESSURES FROM TABLE 1609.6B ARE -59.2 | | AT PERIMETER AREAS AND -89.0 AT THE | | CORNERS. SUBMIT PRODUCT APPROVAL FOR | | ROOFING MATERIAL THAT HAS ADEQUATE | | DESIGN PRESSURES. SEE COMMENT #4 ON LAST | | REVIEW. | | | | 3) FBC 11-4.5.1 REQUIRES CHANGES IN | | LEVEL ON AN ACCESSIBLE ROUTE GREATER | | THAN 1/2 INCH SHALL BE ACCOMPLISHED BY | | MEANS OF A RAMP THAT COMPLIES WITH | | SECTION 11-4.7 OR 11-4.8. SPECIFY THE | | LOCATION OF RAMPS ON THE ACCESSIBLE | | ROUTES TO THE OFFICES. SPECIFY THE SLOPE | | OF THE RAMPS, ETC. COMMENT #7 ON LAST | | REVIEW. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|