2006-05-15 00:00:00 | DENIED BY BUILDING |
| |
| 1) SPECIFY THE CONSTRUCTION TYPE AND |
| TYPE OF OCCUPANCY BASED ON THE 2004 |
| FLORIDA BUILDING CODE. SEE #3 FROM |
| PERVIOUS COMMENTS. |
| |
| 2)THE WINDLOAD DATA ON THE PLAN |
| REFRENCES FBC 1606.1.7. THIS SECTION HAS |
| CHANGED IN THE 2004 FBC TO 1603.1.4. |
| PLEASE CORRECT. |
| |
| 3) SPECIFY THE FASTENING REQUIREMENTS |
| FOR THE 3/4" PLYWOOD ROOF SHEATHING AS |
| REQUIRED BY 2004 FBC TABLE 2304.9.1. |
| #31, WHICH REQUIRES FASTENER SPACING OF |
| 4" OC AT COMPONENT AND CLADDING ROOF |
| ZONE 3. SEE COMMENT #8 FROM PREVIOUS |
| REVIEW. |
| |
| 4) THE PRODUCT APPROVAL SUBMITTED FOR |
| THE ROOFING MATERIAL DOES NOT MEET THE |
| REQUIRED UPLIFT PRESSURE. PRODUCT |
| APPROVAL LISTS MAXIMUM DESIGN PRESSURE |
| AS -45 PSF WITH NO ENHANCED FASTENING |
| ALLOWED. THE REQUIRED PRESSURES FROM |
| TABLE 1609.6B ARE -59.2 AT PERMITER |
| AREAS AND -89.0 AT THE CORNERS. SUBMIT |
| APPROPRIATE PRODUCT APPROVAL. |
| |
| 5) THE FIGURES GIVEN IN THE COMPONENT |
| AND CLADDING TABLE ON THE PLANS ARE FOR |
| A STRUCTURE WITH A ROOF SLOPE GREATER |
| THAN 10 DEGREES. THESE STRUCTURES HAVE |
| SLOPES LESS THAN 10 DEGREES. PLEASE |
| CORRECT. SEE FBC TABLE 1609.6B. |
| |
| 6) THE PLANS REFERENCE ASCE 7-98. THE |
| AMENDMENTS TO THE 2004 FBC CHANGED THE |
| EDITION OF ASCE 7 TO ASCE 7-02. |
| |
| 7) INDICATE HOW THE ACCESSIBLE ROUTE |
| WILL BE MAINTAINED INTO OFFICE 1 FROM |
| THE EXTERIOR AND OFFICE 2 FROM BOTH THE |
| EXTERIOR AND INTERIOR AFTER THE SLABS |
| ARE RAISED (FBC 11-4.1.6). SEE COMMENT |
| #12 FROM PREVIOUS REVIEW. SPECIFY THE |
| ELEVATION CHANGES AND PROVIDE DETAILS OF |
| RAMPS, ETC. |
| |
| 8) SUBMIT TWO COPIES OF PRODUCT |
| APPROVALS FOR EXTERIOR DOORS THAT HAVE |
| BEEN APPROVED BY THE DESIGNER OF RECORD |
| PER FBC 106.3.3 AS AMENDED BY CITY OF |
| WPB. |
| |
| 9) TWO COPIES OF ALL PRODUCT APPROVALS |
| ARE REQUIRED. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| |
| |
| |
| |